SJC Home
Clearance Sheet C2019-005506*006

 Department IssuesSigned OffIntl

Plan for a 9466sf interior remodel for a business occupancy located within a 2 story office building that is provided with fire sprinklers and a fire alarm.  The plans is designed and was reviewed as a business occupancy.  The plans are APPROVED with important notes below. 


                                                        
Reviewed using FFPC 6th edition effective Dec. 31, 2017.
Reviewer: PJ Webb 904 209 1744
 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

3/13/2020 PWebb

Pocket doors are indicated on the plans for a couple locations.  These are OK, however ensure that the doors are operable from both sides (handle) per NFPA 101:7.2.4.1 (4)(C)

3/13/2020 PWebb

Per a discussion with the electrical engineer Bryan Shaffer, exit access directional signs will need to be added at the intersection of the passage 102 circle on both sides of the circle in front of the nurses stations.  Basically at the intersection of the circle and the hallways that lead to the exit doors. 

The engineer indicated that he will ensure that these are followed through.  This will be verified at the time of final.   

3/13/2020 PWebb

INFORMATIONAL ONLY NO RESPONSE NECESSARY:
The system(s) outlined in this set of plans is conceptual.

A HOLD has been placed at framing (105) until either: a) a permit has been pulled or b) a letter submitted from respective system contractor indicating no work to be done to the existing system:
- fire alarm system
- fire sprinkler system

3/13/2020 PWebb