SJC Home
Clearance Sheet C2019-005506*004

 Department IssuesSigned OffIntl

Review of a revision to the previously approved plans, that consist of a change in layout and an addition of a wall.  The sheets revised are G1.1d, G4.1, A2.1d, A8.21d, A10.1.1d, 1N2.1d, M2.1dd, P2.1dwd, FP2.10d, E0.1d, E2.1ld, E2.3pd, E2.5sd, and E8.7. The revision is APPROVED as submitted with important note below. 


                                                        
Reviewed using FFPC 6th edition effective Dec. 31, 2017.
Reviewer: PJ Webb 904 209 1744
 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

10/26/2020 PWebb

HOLDS

Since the layout of the space has changed and a wall added, I have re-instituted holds for fire alarm and fire sprinkler permits.  Provide revisions to the alarm and sprinkler system indicating the work needed to bring the space into compliance or provide letters from the respective contractors to me indicating that no work will be necessary. 

10/26/2020 PWebb