| | Department Issues | Signed Off | Intl |
|
|
Plans for a 1500 sf interior remodel within an existing building that does have fire sprinklers and a fire alarm system. The space is indicated on the plans as mixed assembly and business. The plan was reviewed as business. Plans NOT APPROVED for the following reasons.
Note: Attempted to contact architect and engineer, got general mailbox.
Reviewed using FFPC 6th edition effective Dec. 31, 2017. Reviewer: PJ Webb 904 209 1744 To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
|
| |
|
|
The plan summary indicates that the space is designed as mixed assembly and business. Please take a second look at the classification. Unless I am missing something, I do not see an assembly component. If it is truly an assembly, the space would require 2 means of egress. Modify the plans accordingly.
|
| |
|
|
Ensure that doors 1206 (x2) and 1204 are provided with closers and latches since they are in a smoke partition. NFPA 101:8.4.3.5 and 8.5.4.4. and 8.5.4.3.
|
| |
|
|
At the time of fire final be prepared to provide a copy of the manufacturer specification sheets to the fire inspector showing that each interior finish will meet:
- wall and ceiling finish will meet Class A, B or C. 101:38.3.3.2.2
- floor finish shall meet either: a) ASTM D 2859 for carpet and carpet like materials or b) has a minimum critical radiant flux of .1 W/cm2 for non carpet flooring. 101:38.3.3.3.3.
If there are multiple finishes, label each spec sheet identifying each product, its location AND highlight the area showing illustrating it meets the applicable Code requirement.
|
| |
|
|
There are two HVAC ducts that penetrate the smoke barrier as indicated on sheet M2.1dd. I do not see an indication of proposed smoke dampers. Please identify on the plans. Ensure that the dampers are rated for at least class 2 smoke leakage and have an elevated temperature rating of at least 250 degrees. NFPA 101:8.4.6.2 and 8.4.6.3.
|
| |
|
|
INFORMATIONAL ONLY NO RESPONSE NECESSARY: The system(s) outlined in this set of plans is conceptual.
A HOLD has been placed at framing (105) until either: a) a permit has been pulled or b) a letter submitted from respective system contractor indicating no work to be done to the existing system: - fire alarm system - fire sprinkler system
|
| |