Clearance Sheet C2019-005506*002

 Department IssuesSigned OffIntl

Plans for a revision to the previous plans to change the basketball court surface of the Airnasium from concrete to using Thor Mod Outdoor interlocking tiles.  The flooring meets the requirements of ASTM E 648 at .13W/cm2 which exceeds the requirement of .10 W/cm2.  The revision is APPROVED. 


                                                        
Reviewed using FFPC 6th edition effective Dec. 31, 2017.
Reviewer: PJ Webb 904 209 1744
 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

10/26/2020 PWebb