Clearance Sheet C2019-005506*002

 Department IssuesSigned OffIntl

1) Plans for a 84600sf interior build out for a YMCA that will be located in an existing 2 story building that is equipped with a fire alarm and fire sprinkler system.  The first floor portion will be business at 43,200sf. The second floor is assembly at 41400sf.  The plans are Not Approved for the following reasons.   

--------------------

Plans APPROVED.  Note there are some things in red in the following comments that need to be addressed prior to final.  They have been highlighted Maroon for your convenience.  Plan APPROVED.  PJW Monday, April 13, 2020 


                                                        
Reviewed using FFPC 6th edition effective Dec. 31, 2017.
Reviewer: PJ Webb 904 209 1744
 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

4/13/2020 PWebb

2) The plans were submitted as Business and Assembly.  The kids zone, infant area, and teen center meet the definition of Daycare Occupancy as indicated in NFPA 101:3.3.190.4.  Ensure that the plans meet the requirements for daycare and indicate this in the plan summary.  Also note whether the daycare will be mixed use or separated use.  If mixed the entire 1st floor space will need to meet all occupancy requirements.  If separated, show the separation and egress that does not intermingle with the others. 

----------------------

Plans resubmitted as multiple mixed use, Business, Assembly, and Daycare on the first floor.   

4/13/2020 PWebb

3) Provide the square footage and occupant load for the Teen area, Kids Zone, infant area, group cycle (2204) and group exercise (2203). 

----------------

Provided on RTC and LS plans.  PJW Monday, April 13, 2020  

4/13/2020 PWebb

4) Multipurpose Room

The occupant load used for the 1st floor multipurpose room is 50 which is for exercise rooms with equipment or concentrated business.  What will the space be used for? 

---------------

The designation of the space was changed to Multipurpose with a factor of 15 resulting in 60 occupants.  Sufficient egress provided.   PJW Monday, April 13, 2020

 

4/13/2020 PWebb

5) Provide all FFE Plans (furniture, fixtures and equipment) for all areas, including Multipurpose room, daycare area, and the gym (assembly area) upstairs.  Ensure that your life safety plan egress routes correspond. 

4/13/2020 PWebb

6) The entire 2nd floor gym are is calculated at 50 sf/person which is exercise rooms with equipment.  Show the locations of all exercise equipment that supports this factor.  If there are open exercise areas that do not have equipment in them they will need to be calculated at a factor of 15.  Provide the occupant load for each exercise space on the plans.  Show panic hardware on the door schedule as applicable.   

------------------

Exercise equipment is indicated on the plans.  The occupant load indicated exceeds 100 therefore both exits from the space will require panic hardware.  It is not clear on the shell plans if the existing doors were installed with panic hardware.  Ensure that both doors have panic hardware installed prior to final.  This includes the stairwell door and the double doors leading into the center vestibule area.  This will be verified at final.  PJW Monday, April 13, 2020

4/13/2020 PWebb

7) The locations for the following daycare requirements are based on the assumption that the daycare area will be treated as a separated occupancy.  If mixed use (non separated use) is utilized, the requirements will apply to the entire floor. 

-------

Space designed as multiple/mixed occupancy.  The requirements will be complied with throughout the buildout on the first floor.  PJW Monday, April 13, 2020

4/13/2020 PWebb

8) Daycare- Door latches

Door latches to closets, storage areas, etc. must be able to be opened from the inside.  NFPA 101:16.2.2.4.  Ensure storage room 1121 can be opened from the inside at all times. 

----------------------

Per RTC all storage doors provide free egress.  PJW Monday, April 13, 2020 

4/13/2020 PWebb

9) Daycare- Bathroom Doors

Bathroom doors must be designed to allow opening from the outside when locked, by an opening device that is readily available to staff.  demonstrate on the plans. 

------------------

Per RTC all bathroom doors are provided with hardware that is equipped with an emergency release from the outside using an emergency pin that will be provided to staff.  (AU 5402LN) PJW Monday, April 13, 2020

4/13/2020 PWebb

10) Daycare- Emergency lights

Note the strict requirements for daycare emergency lighting as indicated in NFPA 101:16.2.9 (1-5)

-------------------

Per RTC, The lights were reviewed and meet the requirements of the above.  PJW Monday, April 13, 2020

4/13/2020 PWebb

11) Door hardware

The plans do not include the hardware information that is referenced in the door schedule.  If not identified on the plans, provide the applicable sheets from the manual. 

4/13/2020 PWebb

12) INFORMATIONAL ONLY NO RESPONSE NECESSARY:
The system(s) outlined in this set of plans is conceptual.

A HOLD has been placed at framing (105) until either: a) a permit has been pulled or b) a letter submitted from respective system contractor indicating no work to be done to the existing system:
- fire alarm system
- fire sprinkler system
- Rubber gym tile Specifications.

- Revision to emergency lighting addressing comment 14.  PJW Monday, April 13, 2020 

 

4/13/2020 PWebb

13) Interior finish

Please indicate the required interior floor, wall and ceiling finish according to the Assembly, Daycare, and Business occupancy chapters.  The most stringent will apply throughout (unless the daycare is separated).  Provide specification sheets for the finishes if available.  If not have them available on site for the inspector.   

-----------------

Some information was provided now, the remaining will be available at the time of final inspection.  Please maintain all documents on site for the building finishes.  PJW Monday, April 13, 2020

4/13/2020 PWebb

14) Emergency lights. 

Overall the emergency light coverage looks really good utilizing the battery backup normal lighting.   Please take a look at toilet 1103, toilet 1112, check in area 1116. It appears that they will need additional coverage.   Also see comment 10 about Daycare emergency lights. 

-----------------

Lighting has not been added in the above areas.  The plans indicate that the deficiencies will be fixed in a future revision. 
Also I do not see an exit sign for the second exit from the group exercise 2203.  It may be existing but it is not indicated as such as it is for the group cycling room.   Ensure that this sign is in place since both exits are required due to occupant load. 
PJW Monday, April 13, 2020. 

4/13/2020 PWebb

15) The plans indicates that motion sensors will be used in the areas of egress. At time of fire final be prepared to show compliance with NFPA 101 7.8.1.2.2:

(1) switch controllers must be listed (2) switch controllers equipped for fail-safe operation and evaluated for this purpose (3)  timers be set for a minimum 15 minute duration. (4)  motion sensor be activated by any occupant movement in the area served by lighting units (5) If building has a fire alarm, activation of fire alarm must activate the switch controller (6)  lighting control device may not turn off any lights realized upon for activation of photo luminescent exit signs or path markers (7) Lighting control devices may not turn off any battery equipped emergency luminaries, unit equipment or exit signs

-----------------------

Per RTC, this will be provided by future revision.  PJW Monday, April 13, 2020

4/13/2020 PWebb

16) Provide specification sheets for the proposed rubber tile. 

--------------

Not provided, hold placed on the permit for this information.  No inspections will be completed past framing until this information is received.  PJW Monday, April 13, 2020

4/13/2020 PWebb