Be prepared to provide the following at time of fire final to the fire inspector.
- interior wall and ceiling finish in exit access corridor shall meet class A or B. 101:38.3.3.2
- interior wall and ceiling finish everywhere else shall meet Class A, B or C. 101:38.3.3.2.2
- floor finish throughout shall meet either: a) ASTM D 2859 for carpet and carpet like materials or b) has a minimum critical radiant flux of .1 W/cm2 for non carpet flooring. 101:38.3.3.3.
If there are multiple finishes, label each spec sheet identifying each product, its location AND highlight the area showing illustrating it meets the applicable Code requirement.