Plan reviewed for interior build out of 1435sf new doctors office in an existing construction type IIIB non sprinklered building. Reviewed as new business using FFPC 6th edition effective Dec. 31, 2017.

Reviewer: 
Victoria Vitori 904 209 1748
Anthony Gedris  904-209-1741

 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

8/9/2019 VVitori

Be prepared to provide the following at time of fire final to the fire inspector.

- interior wall and ceiling finish in exit access corridor shall meet class A or B. 101:38.3.3.2

- interior wall and ceiling finish everywhere else shall meet Class A, B or C. 101:38.3.3.2.2

- floor finish throughout shall meet either: a) ASTM D 2859 for carpet and carpet like materials or b) has a minimum critical radiant flux of .1 W/cm2 for non carpet flooring. 101:38.3.3.3.

If there are multiple finishes, label each spec sheet identifying each product, its location AND highlight the area showing illustrating it meets the applicable Code requirement.

8/9/2019 VVitori