DO NOT FORGET *** A HOLD AT 101 FOUNDATION HAS BEEN ADDED FOR THIS TO BE ADDRESSED.
An ENGINEERED signed and sealed Design Criteria for the fire alarm system over $5000.00 is required to be submitted with the general construction documents. FBC 105.3.1.2 We are unable to approve the plan until this information is provided. (The Design Criteria is not a full set of shop drawings.) THIS IS WHAT IS REQUIRED BY FLORIDA ADMINISTRATIVE CODE 61G15-32.008,(A-O) Design of Fire Alarms and Detection Systems.
DO NOT FORGET ***A HOLD AT 101 FOUNDATION HAS BEEN ADDED FOR THIS TO BE ADDRESSED.
An ENGINEERED sealed Design Criteria for a fire sprinkler system exceeding 49 heads is required to be submitted with the general construction documents. We are unable to approve the plan until this information is provided. (FAC 61G15-32.002(5)) (The signed and sealed design criteria is the general guidelines with design and scope of the sprinkler system. It is not a full set of shop drawing.) THIS IS WHAT IS REQUIRED BY FLORIDA ADMINISTRATIVE CODE 61G15-32.004, (A-M) as of June 19th, 2015, Design of Water Based Fire Protection Systems.