| | Department Issues | Signed Off | Intl |
|
|
Plan reviewed for new 6500sf mercantile construction type VB fire sprinklered SHELL ONLY. It will have 4 separate suites with slab only and a separate fire alarm/ riser room. Reviewed using FFPC 6th edition effective Dec. 31, 2017.
Reviewer: Victoria Vitori 904 209 1748 Anthony Gedris 904-209-1741
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
|
6/25/2019
| VVitori |
|
|
INFORMATIONAL ONLY NO RESPONSE NECESSARY: The system(s) outlined in this set of plans is conceptual.
A HOLD has been placed at framing (105) until a permit has been pulled for the:
- fire alarm system - fire sprinkler system - fire underground
|
6/25/2019
| VVitori |
|
|
A HOLD AT 101 FOUNDATION HAS BEEN ADDED FOR THIS TO BE ADDRESSED.
An ENGINEERED signed and sealed Design Criteria for the fire alarm system over $5000.00 is required to be submitted with the general construction documents. FBC 105.3.1.2 We are unable to approve the plan until this information is provided. (The Design Criteria is not a full set of shop drawings.) THIS IS WHAT IS REQUIRED BY FLORIDA ADMINISTRATIVE CODE 61G15-32.008,(A-O) Design of Fire Alarms and Detection Systems.
|
6/25/2019
| VVitori |
|
|
A HOLD AT 101 FOUNDATION HAS BEEN ADDED FOR THIS TO BE ADDRESSED. An ENGINEERED sealed Design Criteria for a fire sprinkler system exceeding 49 heads is required to be submitted with the general construction documents. We are unable to approve the plan until this information is provided. (FAC 61G15-32.002(5)) (The signed and sealed design criteria is the general guidelines with design and scope of the sprinkler system. It is not a full set of shop drawing.) THIS IS WHAT IS REQUIRED BY FLORIDA ADMINISTRATIVE CODE 61G15-32.004, (A-M) as of June 19th, 2015, Design of Water Based Fire Protection Systems.
|
6/25/2019
| VVitori |