SJC Home
Clearance Sheet C2019-003105

 Department IssuesSigned OffIntl

Plan reviewed for revision to 4 pages (A0.0, SP1.1, A1.1, S2.1). Scope of revision SP1.1 is site related. Scope of A1.1 is removes 2 - tenant separation walls. S2.1 revises foundation plan. Reviewed using FFPC 6th edition effective Dec. 31, 2017.

Reviewer: 
Victoria Vitori 904 209 1748
Anthony Gedris 904-209-1741
 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

8/8/2019 VVitori

Make sure site plan is updated with DRC.

8/8/2019 VVitori

DO NOT FORGET *** A HOLD AT 101 FOUNDATION HAS BEEN ADDED FOR THIS TO BE ADDRESSED.

An ENGINEERED signed and sealed Design Criteria for the fire alarm system over $5000.00 is required to be submitted with the general construction documents. FBC 105.3.1.2  We are unable to approve the plan until this information is provided. (The Design Criteria is not a full set of shop drawings.) THIS IS WHAT IS REQUIRED BY FLORIDA ADMINISTRATIVE CODE 61G15-32.008,(A-O) Design of Fire Alarms and Detection Systems.

8/8/2019 VVitori

DO NOT FORGET ***A HOLD AT 101 FOUNDATION HAS BEEN ADDED FOR THIS TO BE ADDRESSED.

An ENGINEERED sealed Design Criteria for a fire sprinkler system exceeding 49 heads is required to be submitted with the general construction documents. We are unable to approve the plan until this information is provided. (FAC 61G15-32.002(5)) (The signed and sealed design criteria is the general guidelines with design and scope of the sprinkler system. It is not a full set of shop drawing.) THIS IS WHAT IS REQUIRED BY FLORIDA ADMINISTRATIVE CODE 61G15-32.004, (A-M) as of June 19th, 2015, Design of Water Based Fire Protection Systems.

8/8/2019 VVitori