| | Department Issues | Signed Off | Intl |
|
|
#1
per fbc chapter one plans need to be signed & sealed
|
| |
|
|
#2
per fbc one need code summary with use per fbc chapter 3 & type construction
|
| |
|
|
#3
life safety plan needs egress to accessible route / parking
|
| |
|
|
#4
energy sheet project summary needs st johns county 651000
|
| |
|
|
#5
energy sheets list no exterior lighting / see elec. plans & panel schedules
|
| |
|
|
#6
per fec 405.2.1 occupancy sensors are required in all rooms including rest rooms
|
| |
|
|
#7
energy sheets list only one water heater & gallons ?
|
| |
|
|
#8
per fac need all turning radius , heights , clearances , shower accessibility , 7" to 9" to center in front of the water closet
per fac 604.7 & 608
|
| |
|
|
#9
per fac 214 washing machines & dryers require accessibility fac 611
|
| |
|
|
#10
per nec 110.24 service equip shall be marked with the max. fault current available
|
| |
|
|
#11
need lint interceptor detail & locations
|
| |
|
|
#12 per fac 216.3 signs are required to direct customers & visitors to laundry & rest rooms with showers
|
| |