SJC Home
Clearance Sheet C2019-001630*001

 Department IssuesSigned OffIntl

Plans for a revision to sheets E101, E102, E103, E104, and E402.  The revision is to address an open emergency light hold where I was waiting on information regarding the compliance with NFPA 101:NFPA 101:7.9.2.3(2)and(3). To address this the revision indicates that the emergency lighting fixtures are alternated between two different LS circuits.  This meets the requirements indicated above.   


                                                        
Reviewed using FFPC 7th edition effective Dec. 31, 2020.
Reviewer: PJ Webb 904 209 1744 pwebb@sjcfl.us
 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
 
For questions regarding comments you may reach me at either: 904 209 1744 or pwebb@sjcfl.us.

6/23/2022 PWebb

Informational Note:

A hold still remains for a revision to the mechanical plans identifying damper access.  See original plan comments. 

6/23/2022 PWebb