SJC Home
Clearance Sheet C2019-001630*001

 Department IssuesSigned OffIntl

Plans for a 147 device addressable voice evacuation fire alarm system for a large ALF/Memory Care facility. 


                                                        
Reviewed using FFPC 7th edition effective Dec. 31, 2020.
Reviewer: PJ Webb 904 209 1744 pwebb@sjcfl.us
 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

5/17/2022 PWebb

RESUBMITTING: Please make necessary changes and resubmit the complete permit application package. Response to comments / plans / specifications must be submitted to the Permit Center as a resubmission for the original project.

Effective 1/01/2022 you must include a written response to comments summary to clarify and illustrate corrections on plans (bubbling, highlighting, or notations are best). Please use the Florida Fire Prevention Code 7th Ed. for all code reference in a response to comments. You are required to remove old pages and reinsert the new pages.

Resubmittals will not be approved without a response to comments. 

5/17/2022 PWebb

1) Edwards io1000D and Edwards io64 panels are indicated.  Which is being used?

----------------

RTC indicates that both panels previously listed are being upgraded to EST 3X for both buildings.  PJW Tuesday, May 17, 2022

5/17/2022 PWebb

2) Visual appliances are required in all offices and all client living units per NFPA 101:9.6.3.5.  Also what is workroom 504 used for?  This may require a device as well. 

-------------

Visual devices added as indicated.  PJW Tuesday, May 17, 2022

5/17/2022 PWebb

3) Where will the voice evacuation panel be located?

------------

Per RTC the evac function is integrated into the EST3x panel located in room 515.  PJW Tuesday, May 17, 2022

5/17/2022 PWebb

4) Provide visible appliances on at least all 4 walls of the exterior courtyards.   The indicated coverage is sufficient if the space were indoors, however it is the opinion of this office that being outside in direct sunlight, the reflective properties of the strobes will be lost therefore requiring direct line of sight. 

---------------

Devices added as indicated.  PJW Tuesday, May 17, 2022

5/17/2022 PWebb

5) What are the square symbols with letters inside such as RM1, CC1, and TCDR?  I do not see them indicated on the legend or by note. 

------------------

Devices added to legend on sheet FA-2.  PJW Tuesday, May 17, 2022

5/17/2022 PWebb

6) Indicate the distance from the ceiling for the sleeping room visible appliances.  NFPA 72:18.5.5.7.2. 

--------------

Note 14 added to drawing FA-1.  PJW Tuesday, May 17, 2022

5/17/2022 PWebb

7) Demonstrate tie in to activate the lighting control devices (motion sensors) as indicated in NFPA 101:7.8.1.2.2(5).

--------------

Information added to sheet FA-5.  PJW Tuesday, May 17, 2022

5/17/2022 PWebb