| | Department Issues | Signed Off | Intl |
|
|
Plans for a 147 device addressable voice evacuation fire alarm system for a large ALF/Memory Care facility.
Reviewed using FFPC 7th edition effective Dec. 31, 2020. Reviewer: PJ Webb 904 209 1744 pwebb@sjcfl.us To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
|
| |
|
|
RESUBMITTING: Please make necessary changes and resubmit the complete permit application package. Response to comments / plans / specifications must be submitted to the Permit Center as a resubmission for the original project.
Effective 1/01/2022 you must include a written response to comments summary to clarify and illustrate corrections on plans (bubbling, highlighting, or notations are best). Please use the Florida Fire Prevention Code 7th Ed. for all code reference in a response to comments. You are required to remove old pages and reinsert the new pages.
Resubmittals will not be approved without a response to comments.
|
| |
|
|
1) Edwards io1000D and Edwards io64 panels are indicated. Which is being used?
|
| |
|
|
2) Visual appliances are required in all offices and all client living units per NFPA 101:9.6.3.5. Also what is workroom 504 used for? This may require a device as well.
|
| |
|
|
3) Where will the voice evacuation panel be located?
|
| |
|
|
4) Provide visible appliances on at least all 4 walls of the exterior courtyards. The indicated coverage is sufficient if the space were indoors, however it is the opinion of this office that being outside in direct sunlight, the reflective properties of the strobes will be lost therefore requiring direct line of sight.
|
| |
|
|
5) What are the square symbols with letters inside such as RM1, CC1, and TCDR? I do not see them indicated on the legend or by note.
|
| |
|
|
6) Indicate the distance from the ceiling for the sleeping room visible appliances. NFPA 72:18.5.5.7.2.
|
| |
|
|
7) Demonstrate tie in to activate the lighting control devices (motion sensors) as indicated in NFPA 101:7.8.1.2.2(5).
|
| |