Clearance Sheet C2019-001625*001

 Department IssuesSigned OffIntl

Plans for a revision to the previously approved plans to provide generator specifications for the life safety generator that is being installed. The generator is a Generac SD150 150KW with a 1076 gallon double wall diesel saddle tank, indicated to have a 96 hour run time with a full fuel load.    

Note: Per supervisor the installation of the bollards will be verified at the time of final.  See comment below for requirements. 


                                                        
Reviewed using FFPC 7th edition effective Dec. 31, 2020.
Reviewer: PJ Webb 904 209 1744 pwebb@sjcfl.us
 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
 
For questions regarding comments you may reach me at either: 904 209 1744 or pwebb@sjcfl.us.

6/15/2022 PWebb

Ensure that the bollards are installed in accordance with the below. 

 

60.5.1.9 Protection from Vehicles.

60.5.1.9.1 

Guard posts or other approved means shall be provided to protect the following where subject to vehicular damage:

1.      Storage tanks and connected piping, valves, and fittings

2.      Storage areas containing tanks or portable containers except where the exposing vehicles are powered industrial trucks used for transporting the hazardous materials

3.      Use areas

60.5.1.9.2 

Where guard posts are installed, the posts shall meet the following criteria:

1.      They shall be constructed of steel not less than 4 in. (102 mm) in diameter and concrete filled.

2.      They shall be spaced not more than 4 ft (1.2 m) between posts on center.

3.      They shall be set not less than 3 ft (0.9 m) deep in a concrete footing of not less than a 15 in. (381 mm) diameter.

4.      They shall be set with the top of the posts not less than 3 ft (0.9 m) above ground.

5.      They shall be located not less than 3 ft (0.9 m) from the tank.

 

6/15/2022 PWebb