Clearance Sheet C2019-001625*001

 Department IssuesSigned OffIntl

Plans submitted with a revision sheet for truss package calcs and shop drawings, and food service drawings.  The food service drawings submitted are as follows: FS.01 through FS.17, which include some kitchen hood information.  The only plans that have minor revision clouding are FS.9, FS.13, FS.14, and FS.15.   Is this intended to serve as a revision to the above sheets?  If yes provide an itemized revision narrative indicating the changes and or clouding. 

If the food service plans are intended to serve as a submittal for the kitchen hood, it will need to be separated from the revision and submitted separately with a kitchen hood application.   Left message with contact. 

-------------------

Heard back from contact, the Food Service sheets are intended to serve as the hood submittal.  Explained to the contact that they would need to be separated and submitted separately.  Returned plans to Dawn.  PJW Wednesday, December 8, 2021 

-------------------

The food service plans and the truss information were separated.  This current revision is just for the truss package, no Fire Marshal issues.   The food service plans were submitted as a separate revision today, to add the food service sheets to the approved construction plans.  There was no indication on that revision sheet that it was intended as the hood submittal, no hood application was provided and the food service plans did not include any hood information to be reviewed as a hood permit.  That revision was NOT reviewed and approved as the hood submittal, it was just to add the sheets to the record as indicated on the revision sheet.  PJW Thursday, January 20, 2022


                                                        
Reviewed using FFPC 7th edition effective Dec. 31, 2020.
Reviewer: PJ Webb 904 209 1744
 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

1/20/2022 PWebb