Plans for a underground fire main for Building 1 that begins at the 6" backflow preventer (off of the 8" site main) and includes approximately 120' of 6" DR18 pipe, tying into a stainless steel riser sweep terminating 1'AFF.  The FDC is a yard FDC tied into the underground main.  The underground is included on a single set of plans with the site private mains and building 2 underground, so I have included the comments for the entire project under both building reviews.   

 
                                                        
Reviewed using FFPC 7th edition effective Dec. 31, 2020.
Reviewer: PJ Webb 904 209 1744
 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

 

RESUBMITTING: Please make necessary changes and resubmit the complete permit application package. Response to comments / plans / specifications should be submitted to the Permit Center as a resubmission for the original project unless other arrangements are made with the Fire Plan Reviewer or the Fire Plan Review Supervisor.

To help speed the review process you should include a written response to comments summary to clarify and/or illustrate corrections on plans (bubbling, highlighting, or notations are best). Please use the Florida Fire Prevention Code 7th Ed. for all code reference in a response to comments. You are required to remove old pages and reinsert the new pages.

The numbered items require a response or plans to be updated to complete the review.

 

1) Indicate the pipe depth of cover per NFPA 24:4.1.3 (8)(H) in accordance with NFPA 24:10.4.2.2.

 

2) Identify the pipe lengths on the plans per NFPA 24:4.1.3 (8)

 

3) Provide hydraulic calculations demonstrating that the proposed mains can supply the total demand.  NFPA 24:5.2.1

 

4) FDC connection on piping up to 2 inches shall be equipped with a Double Clapper Siamese Connection.

FDC connections on piping LARGER than 2 inches shall be equipped with a five (5) inch Storz connection and shall have a 30 degree downward deflection.

This applies to all FDC’s regardless being on a building or free standing.

NFPA 24:5.9.1.2, and 5.9.2.4

 

5) Provide plan details for the fire hydrants and Fire Department connections.  Ensure hydrant detail is in compliance with NFPA 24
:7.3. 

 

6) I did not see an automatic drain valve indicated on the plans or specs for the FDC.  NFPA 24:5.9.4.1.  Show on FDC detail as well.

 

7) Show on the plans how the backflow preventers (3) will be protected from freezing.  NFPA 24:6.5.2.  This is indicated on the plan for the 8" backflow, but not the 2, 6 inch.  Provide specifications for the method used. 

 

8) Is the WATTS LF757DCDA being used at all 3 locations?

 

9) License

Our records indicate that the Class V license for Horace B. Clark is expired.  Provide current class V license or have a currently licensed contractor submit for permit.  Contact a fire permit technician for further information.