| | Department Issues | Signed Off | Intl |
|
|
#1
per fbc chapter one a life safety plan is required / egress arrows & exit directional signage
|
5/8/2019
| fbecza |
|
|
#2
per fac 216.3 signs are required to direct customers & visitors to interior facilities & spaces
|
| |
|
|
#3
need hvac drawing with supplies and returns in new & renovated spaces
|
| |
|
|
#4
need locations of electric panels [new panel] on plans not loose 8.5 x 11
|
| |
|
|
#5
per nec 110.24 elec. equip. shall be marked with the max. fault current available
|
| |
|
|
#6
per fmc401.6 contaminants cannot be recirculated / duct & exhaust need to show that
|
| |