Clearance Sheet C2018-008687*001

 Department IssuesSigned OffIntl

Plans for a 14"6" type I CaptiveAire kitchen hood with welded duct for a restaurant.  The plans are NOT APPROVED for the following reasons. 

-------------

Plans APPROVED.  PJW Friday, October 02, 2020


                                                        
Reviewed using FFPC 6th edition effective Dec. 31, 2017.
Reviewer: PJ Webb 904 209 1744
 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

10/2/2020 PWebb

RESUBMITTING: Please make necessary changes and resubmit the complete permit application package. Response to comments / plans / specifications should be submitted to the Permit Center as a resubmission for the original project unless other arrangements are made with the Fire Plan Reviewer or the Fire Plan Review Supervisor.

To help speed the review process you should include a written response to comments summary to clarify and/or illustrate corrections on plans (bubbling, highlighting, or notations are best). Please use the Florida Fire Prevention Code 6th Ed. for all code reference in a response to comments. You are required to remove old pages and reinsert the new pages.

The numbered items require a response or plans to be updated to complete the review.

10/2/2020 PWebb

1) What is the wall behind the hood and the cooking equipment constructed of?  Demonstrate compliance with NFPA 96:4.2 or 4.2.3 all the way from the top of the hood to the floor. 

---------

Metal stud per wall type C on sheet A102a PJW Friday, October 02, 2020

10/2/2020 PWebb

2) The exhaust fan does not indicate that it is provided with a hinge, hold open retainer and flexible conduit.  NFPA 96:7.8.2.1, 8.1.2.1. 

-----------

Information provided.  PJW Friday, October 02, 2020

10/2/2020 PWebb

3) Provide manufacturers specification sheets for all equipment and components including but not limited to: upblast fan (8.1.1), filters(6.1.1,6.2.3.1), hood lights(9.2.2),  etc.

10/2/2020 PWebb

4) How will you ensure that the cooking equipment will be returned to its original location?  Demonstrate compliance with NFPA 96:12.1.2.3.1. 

---------

Specs submitted for a dormont positioning system.  PJW Friday, October 02, 2020

10/2/2020 PWebb

5) Provide manufacturers specifications for the cooking equipment.  NFPA 96:12.1.1

-----------

Provided. PJW Friday, October 02, 2020

10/2/2020 PWebb

6) Provide specification sheets for the indicated duct wrap that will be used. 

-----------

Specs provided for Unifrax Fyrewrap Elite 1.5 2 layer wrap.  0" clearance to combustibles.  PJW Friday, October 02, 2020 

10/2/2020 PWebb

7) What size duct will be used?

18" round listed duct.  PJW Friday, October 02, 2020

10/2/2020 PWebb

8) What is the difference between sheets FS-8, FS 8.1, FS8.2 and FS8.3?  They all appear identical. 

-----------

Correct CaptiveAire sheets provided.  PJW Friday, October 02, 2020

10/2/2020 PWebb

Informational Note

Application indicates 3 hoods.  Our office does not review type II hoods.  Scope of this review is for the type I kitchen hood. 

10/2/2020 PWebb