SJC Home
Clearance Sheet C2018-008670

 Department IssuesSigned OffIntl

Plan reviewed for new 7,500 five (5) unit metal building, type IIB construction, Non-Sprinkled. Building will be mixed use Storage (ordinary hazard) and business. Unit's 1 and 2 have built out bathrooms, units 3, 4, and 5 will not have their bathrooms built out. The  future non rated demising walls shown are for future tenants and will not built out at this time.

Reviewed using FFPC 6th edition effective Dec. 31, 2017. NFPA 1 and 101 references are Florida Editions of the code in the FFPC.

Plans are NOT APPROVED.

Reviewer: D. Feagle 904-209-1721

To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.  

 

RESUBMITTING: Please make necessary changes and resubmit the complete permit application package. Response to comments / plans / specifications should be submitted to the Permit Center as a resubmission for the original project unless other arrangements are made with the Fire Plan Reviewer or the Fire Plan Review Supervisor.

To help speed the review process you should include a written response to comments summary to clarify and/or illustrate corrections on plans (bubbling, highlighting, or notations are best). Please use the Florida Fire Prevention Code 6th Ed. for all code reference in a response to comments. You are required to remove old pages and reinsert the new pages.

The numbered items require a response or plans to be updated to complete the review.

 

1) No door and hardware schedule provided.

Provide door and hardware schedule.

 

INFORMATIONAL ONLY NO RESPONSE NECESSARY:
At the time of fire final be prepared to provide a copy of the manufacturer specification sheets to the fire inspector showing that each interior finish will meet:

- wall and ceiling finish will meet Class A, B or C. 101:42.3.3.2

If there are multiple finishes, label each spec sheet identifying each product, its location AND highlight the area showing illustrating it meets the applicable Code requirement.

 

INFORMATIONAL ONLY NO RESPONSE NECESSARY:

Development Review Application project description stated this building will be used as an auto parts storage and sales center. That the auto parts and any deconstructed vehicles will be stored indoors and taken off site. Also noted that there will be no lifts or painting on site. That the building will not be used as a service center.