| | Department Issues | Signed Off | Intl |
|
|
Plan reviewed for a 2,782 SF Type VB, Sprinkled, Assembly.
Reviewed using FFPC 7th edition effective Dec. 31, 2020. NFPA 1 and 101 references are Florida Editions of the code in the FFPC.
Reviewer: D. Feagle 904-209-1721, dfeagle@sjcfl.us
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
--------------------------------------
Tuesday, March 22, 2022 DF: Review of 1st resubmittal - No Response to comments provided. No review conducted.
|
| |
|
|
RESUBMITTING: A. Make necessary changes and resubmit everything in person to the Permit Center. B. Once at the Permit Center swap out altered pages in EACH plan set (job and office). One copy of the removed/old pages will need to be resubmitted and labeled "OLD". Do not forget to remove pages for work not associated in this permit. C. Provide a response to comments along with any supporting documentation. - The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comment was addressed. Ex - "top left of page A11" or "Page E1 note 8". - Code responses shall reference Florida Fire Prevention Code 7th Ed. (not Building Code)
|
| |
|
|
1) Demising walls fire rating noted on Sheet A1.0 as 1 hour. According to our records the occupancies on each side of this unit are mercantile (T-Mobile and Fire House Subs). The separation requirements for this occupancy (Assembly) from the mercantile units is 2 hours. 101 - Table 6.1.14.4.1(b).
a) Provide two (2) hour separation for both demising walls and show the rated wall elevation in the plan set. OR,
b) Provide a letter from the fire alarm monitoring company that the Fire Sprinkler Back Flow Preventers control valves and ALL above ground fire sprinkler control valves are being monitored for tamper.
|
| |
|
|
2) Occupant Load shown on sheet G1.0 has the occupant load at 49. The Occupant Load Table uses a factor of 50 (w/equipment) for calculating the Studio (gym) space.
Based on equipment layout and the number of equipment stations (Delta Rigs and Weight Bench’s,) the occupant load for the Studio 49 (Delta rigs – 24, Weight Benches – 24, Instructor Platform – 1). The Lobby occupant load (approximate 315 SF / 7 + receptionist and two benches) places the unit over 50 occupants.
Studio 49 + Lobby 45 + Receptionist 1 + 2 benches (4+4) 8 = 103 persons.
Based on an assembly calculation for the unit, the occupant load is: 103 Persons
Update the Occupant Load Table to reflect the correct occupant load calculations.
|
| |
|
|
3) Hardware set for door 101 (exterior double doors) states existing hardware to remain. Provide information regarding the doors hardware demonstrating that the hardware meets 101:2.2.2.4 / 7.2.1.5.5.
|
| |
|
|
4) Hardware set for door 106 (rear door) states existing hardware to remain. Comment #6 indicates panic hardware to be provided.
Provide spec sheets for the panic hardware demonstrating it complies with 101:7.2.1.7.
|
| |
|
|
5) Doors 102, 103 & 104 do not provide enough information to determine if they comply with 101:7.2.1.5.10.2 (One Releasing Mechanism).
The door’s latching/locking arrangement is required to be of a One Releasing Mechanism (integrated lock and latch) and shall open the door leaf with no more than one (1) releasing operation.
Example: You should be able to open a “locked” door by turning the door handle and push/pull open the door leaf “without” unlocking the door first. The Fire Inspector will at time of the Fire Final verify compliance with this requirement.
|
| |
|
|
6) The laundry room does not appear to be separated from the rest of the unit by a 1 hour fire rated barrier. The door also has a ventilation grill. 101:12.3.2.1.2(2)(a)
a) Demonstrate in the plans the separation of the one hour fire barrier.
b) Remove the ventilation grill or, provide documentation the grill is equipped to comply with the fire rating of the door and prevent passage of smoke and fire/heat.
|
| |
|
|
7) I am unable to find the emergency lighting (EL) manufacturers specs from the make/model information provided on sheet E1.0. The EL provided is via wall packs. With my experience, a typical wall pack EL usually mounted 8' above the floor covers approx. 8' either direction with a 3' wide path parallel with the wall. The EL illumination does not cover the designated egress travel path.
With the layout of the Delta 8 Rigs and the weight lifting benches, emergency lighting is needed in the middle of the room and along the designated egress routes. The lobby egress path especially around the main entrance does not appear to provide adequate EL coverage. 101:12.2.9
a) Provide the EL’s manufacturers specification sheets so I can verify the egress paths noted above. OR,
b) Add additional ELs to cover the egress paths noted above. OR,
c) Provide EL photo-metrics demonstrating coverage of the egress paths noted above.
|
| |
|
|
8) Finish Legend on Sheet A2.0 indicates the ALL areas except for the bathrooms will have Rolled Rubber Flooring.
Provide manufacturer’s specification for the rubber flooring demonstrating it complies with 101:12.3.3.5
|
| |
|
|
9) At the time of fire final be prepared to provide a copy of the manufacturer specification sheets to the fire inspector showing that each interior finish will meet:
- Corridor and Lobby Wall and ceiling finish will meet Class A or B. 101:12.3.3.2
- Assembly (Studio) Wall and ceiling finish will meet Class A, B or C. 101:12.3.3.3
- Floor finish shall meet either: a) ASTM D 2859 for carpet and carpet like materials or b) has a minimum critical radiant flux of .1 W/cm2 for non-carpet flooring. 101:12.3.3.5.3.
If there are multiple finishes, label each spec sheet identifying each product, its location AND highlight the area showing illustrating it meets the applicable Code requirement.
|
| |
|
|
10) Instructor platform on Sheet A1.0 references elevation view on A6.1 (-/A6.1). I am not able to find the platform elevation on Sheet A6.1.
Provide elevation views/details of the platform; size, height, elevation views of the platforms stairs/steps showing they meet 101:7.2.2 and handrails meeting 101:7.2.2.4.
|
| |
|
|
INFORMATIONAL ONLY NO RESPONSE NECESSARY: Air handlers with more than 2000 CFM are required to have duct smoke detectors. NOTE: If there is a FIRE ALARM SYSTEM in the building the duct smoke detector must also be connected to the fire alarm system. (NFPA 90A:6.4.4.2) Where smoke detectors required by 6.4 are installed in a building not equipped with an approved fire alarm system as specified by 6.4.4.2, the following shall occur: 1. Smoke detector activation required by section 6.4 shall cause a visual signal and an audible signal at a normally occupied area. 2. Detector troubles shall be indicated visually or audibly in a normally occupied area identified as air duct
|
| |
|
|
INFORMATIONAL ONLY NO RESPONSE NECESSARY: Make sure that emergency lighting systems are arranged to provide the required illumination automatically in the event of any interruption of normal lighting due to any of the following: NFPA 101 7.9.2.3 (1) Failure of a public utility or other outside electrical power supply (2) Opening of a circuit breaker or fuse (3) Manual act(s), including accidental opening of a switch controlling normal lighting facilities.
|
| |
|
|
INFORMATIONAL ONLY NO RESPONSE NECESSARY: The system(s) outlined in this set of plans is conceptual.
A HOLD has been placed at insulation inspection (109) until either: a) a permit has been pulled or b) a letter submitted from respective system contractor indicating no work to be done to the existing system: - Fire alarm system - Fire sprinkler system - - - -
|
| |