Design Criteria Discrepancies.
Criteria Storage Area- Quick Response 155 degree Brass Uprights
Plan Storage Area- Standard response 200 degree heads.
Criteria- Office .10/1500sf
Plan- Office .10/1036sf using reduction 11.2.3.2.3.
For correction there are 3 options. 1. Revise the plan meeting the design criteria. 2. Have the EOR rubber stamp your plan approved with no exceptions. (not sign and seal. 3. Have the EOR revise the criteria to match the plan.