1) This was a preliminary review of the Classic Car Storage Bldg

1/11/2019 jadams

2) Plans are incomplete to do a complete review need structural engineering for building and foundation   

1/11/2019 jadams

3) Code Summary need to address occupancy as mixed use S-1 and Assembly based on the fire wall separation it would be separated occupancy . FBC 508 .

1/11/2019 jadams

4) Section 406.8 2017 Florida building code storage and repair garages shall be constructed in accordance with the Florida Fire Prevention Code.

1/11/2019 jadams


5) Please provide a Florida product approval list including identifying the glazing assemblies for the 1-hour separation.

1/11/2019 jadams

6) Garage floor shall comply with section 406.3.3 FBC if floor drains are used in automobile storage area an oil separator is required

1/11/2019 jadams

7) Electrical plans need to address and comply with section 405 of the 2017 FBC energy conservation code 

1/11/2019 jadams