Clearance Sheet C2018-007803

 Department IssuesSigned OffIntl

Plans reviewed under Florida Fire Prevention Code 6th edition as new storage and new assembly.  Assembly space occupant load 338.  Storage space occupant load 56.

-------------------

Occupancy classification has been changed to Assembly/Exhibition throughout.  PJW Friday, January 11, 2019

1/11/2019 PWebb

Please provide a window legend.  There are numerous viewing windows installed on the fire rated partition.  Provide rating documentation or how the fire rating will be maintained.

1/11/2019 PWebb

A fire alarm system is required for the building.  This system shall be installed in accordance with NFPA 101, 9.6.1 and 12.3.4.  This shall be noted on the plans.  A separate permit will be required for the system.

--------------

Alarm being installed.  A hold will be placed on the permit for this information.  PJW Friday, January 11, 2019

1/11/2019 PWebb

Sheet M-100 note 8 states HVAC system has return side smoke detectors.  NFPA 90A requires smoke detectors in the supply side on all systems greater than 2,000 CFM.

---------------------

Changes made.  PJW Friday, January 11, 2019

1/11/2019 PWebb

Storage floors shall be graded and drains provided per NFPA 88A, 5.3.2

------------------

Not required.  Not Parking Garage.  PJW Friday, January 11, 2019

1/11/2019 PWebb

A mechanical ventilation system shall be installed in the storage area per NFPA 88A, 6.3

---------------------------

Not required.  Not Parking Garage.  PJW Friday, January 11, 2019

1/11/2019 PWebb

The plans call for a one hour rated separation between the storage and assembly.  According to NFPA 88A, 5.2 this shall be two hour rated.

------------------

Not required.  Not Parking Garage.  Building is entirely Assembly PJW Friday, January 11, 2019

1/11/2019 PWebb

The door rating shall be adjusted to account for the two hour rated separation.

------------------------

Not 2 hour rated.  PJW Friday, January 11, 2019

1/11/2019 PWebb

NEW COMMENT

An ENGINEERED sealed Design Criteria for a fire sprinkler system exceeding 49 heads is required to be submitted with the general construction documents. We are unable to approve the plan until this information is provided. (FAC 61G15-32.002(5)) (The signed and sealed design criteria is the general guidelines with design and scope of the sprinkler system. It is not a full set of shop drawing.) THIS IS WHAT IS REQUIRED BY FLORIDA ADMINISTRATIVE CODE 61G15-32.004, (A-M) as of June 19th, 2015, Design of Water Based Fire Protection Systems.

A hold has been placed (105) for this information. The owner has been notified of this additional comment.

1/11/2019 PWebb

NEW COMMENT

An ENGINEERED signed and sealed Design Criteria for the fire alarm system over $5000.00 is required to be submitted with the general construction documents. FBC 105.3.1.2  We are unable to approve the plan until this information is provided. (The Design Criteria is not a full set of shop drawings.) THIS IS WHAT IS REQUIRED BY FLORIDA ADMINISTRATIVE CODE 61G15-32.008,(A-O) Design of Fire Alarms and Detection Systems.

A hold has been placed (105) for this information.  The owner has been notified of this additional comment.

1/11/2019 PWebb

NEW COMMENT

Please ensure that the vehicles meet the requirement under exhibition in NFPA 101: Section 12.7.5.4.  Inspector will verify at final. 

1/11/2019 PWebb