Plans reviewed under Florida Fire Prevention Code 6th edition as new storage and new assembly. Assembly space occupant load 338. Storage space occupant load 56.
-------------------
Occupancy classification has been changed to Assembly/Exhibition throughout. PJW Friday, January 11, 2019
|
1/11/2019
| PWebb |
|
|
Please provide a window legend. There are numerous viewing windows installed on the fire rated partition. Provide rating documentation or how the fire rating will be maintained.
|
1/11/2019
| PWebb |
|
|
A fire alarm system is required for the building. This system shall be installed in accordance with NFPA 101, 9.6.1 and 12.3.4. This shall be noted on the plans. A separate permit will be required for the system.
--------------
Alarm being installed. A hold will be placed on the permit for this information. PJW Friday, January 11, 2019
|
1/11/2019
| PWebb |
|
|
Sheet M-100 note 8 states HVAC system has return side smoke detectors. NFPA 90A requires smoke detectors in the supply side on all systems greater than 2,000 CFM.
---------------------
Changes made. PJW Friday, January 11, 2019
|
1/11/2019
| PWebb |
|
|
Storage floors shall be graded and drains provided per NFPA 88A, 5.3.2
------------------
Not required. Not Parking Garage. PJW Friday, January 11, 2019
|
1/11/2019
| PWebb |
|
|
A mechanical ventilation system shall be installed in the storage area per NFPA 88A, 6.3
---------------------------
Not required. Not Parking Garage. PJW Friday, January 11, 2019
|
1/11/2019
| PWebb |
|
|
The plans call for a one hour rated separation between the storage and assembly. According to NFPA 88A, 5.2 this shall be two hour rated.
------------------
Not required. Not Parking Garage. Building is entirely Assembly PJW Friday, January 11, 2019
|
1/11/2019
| PWebb |
|
|
The door rating shall be adjusted to account for the two hour rated separation.
------------------------
Not 2 hour rated. PJW Friday, January 11, 2019
|
1/11/2019
| PWebb |
|
|
NEW COMMENT
An ENGINEERED sealed Design Criteria for a fire sprinkler system exceeding 49 heads is required to be submitted with the general construction documents. We are unable to approve the plan until this information is provided. (FAC 61G15-32.002(5)) (The signed and sealed design criteria is the general guidelines with design and scope of the sprinkler system. It is not a full set of shop drawing.) THIS IS WHAT IS REQUIRED BY FLORIDA ADMINISTRATIVE CODE 61G15-32.004, (A-M) as of June 19th, 2015, Design of Water Based Fire Protection Systems.
A hold has been placed (105) for this information. The owner has been notified of this additional comment.
|
1/11/2019
| PWebb |
|
|
NEW COMMENT
An ENGINEERED signed and sealed Design Criteria for the fire alarm system over $5000.00 is required to be submitted with the general construction documents. FBC 105.3.1.2 We are unable to approve the plan until this information is provided. (The Design Criteria is not a full set of shop drawings.) THIS IS WHAT IS REQUIRED BY FLORIDA ADMINISTRATIVE CODE 61G15-32.008,(A-O) Design of Fire Alarms and Detection Systems.
A hold has been placed (105) for this information. The owner has been notified of this additional comment.
|
1/11/2019
| PWebb |
|
|
NEW COMMENT
Please ensure that the vehicles meet the requirement under exhibition in NFPA 101: Section 12.7.5.4. Inspector will verify at final.
|
1/11/2019
| PWebb |