1) This was a preliminary review of the Classic Car Storage Bldg

 

2) Plans are incomplete to do a complete review need structural engineering for building and foundation   

 

3) Code Summary need to address occupancy as mixed use S-1 and Assembly based on the fire wall separation it would be separated occupancy . FBC 508 .

 

4) Section 406.8 2017 Florida building code storage and repair garages shall be constructed in accordance with the Florida Fire Prevention Code.

 


5) Please provide a Florida product approval list including identifying the glazing assemblies for the 1-hour separation.

 

6) Garage floor shall comply with section 406.3.3 FBC if floor drains are used in automobile storage area an oil separator is required

 

7) Electrical plans need to address and comply with section 405 of the 2017 FBC energy conservation code