Plans reviewed under Florida Fire Prevention Code 6th edition as new storage and new assembly. Assembly space occupant load 338. Storage space occupant load 56.
|
| |
|
|
Please provide a window legend. There are numerous viewing windows installed on the fire rated partition. Provide rating documentation or how the fire rating will be maintained.
|
| |
|
|
A fire alarm system is required for the building. This system shall be installed in accordance with NFPA 101, 9.6.1 and 12.3.4. This shall be noted on the plans. A separate permit will be required for the system.
|
| |
|
|
Sheet M-100 note 8 states HVAC system has return side smoke detectors. NFPA 90A requires smoke detectors in the supply side on all systems greater than 2,000 CFM.
|
| |
|
|
Storage floors shall be graded and drains provided per NFPA 88A, 5.3.2
|
| |
|
|
A mechanical ventilation system shall be installed in the storage area per NFPA 88A, 6.3
|
| |
|
|
The plans call for a one hour rated separation between the storage and assembly. According to NFPA 88A, 5.2 this shall be two hour rated.
|
| |
|
|
The door rating shall be adjusted to account for the two hour rated separation.
|
| |