Clearance Sheet C2018-007803

 Department IssuesSigned OffIntl

Plans reviewed under Florida Fire Prevention Code 6th edition as new storage and new assembly.  Assembly space occupant load 338.  Storage space occupant load 56.

 

Please provide a window legend.  There are numerous viewing windows installed on the fire rated partition.  Provide rating documentation or how the fire rating will be maintained.

 

A fire alarm system is required for the building.  This system shall be installed in accordance with NFPA 101, 9.6.1 and 12.3.4.  This shall be noted on the plans.  A separate permit will be required for the system.

 

Sheet M-100 note 8 states HVAC system has return side smoke detectors.  NFPA 90A requires smoke detectors in the supply side on all systems greater than 2,000 CFM.

 

Storage floors shall be graded and drains provided per NFPA 88A, 5.3.2

 

A mechanical ventilation system shall be installed in the storage area per NFPA 88A, 6.3

 

The plans call for a one hour rated separation between the storage and assembly.  According to NFPA 88A, 5.2 this shall be two hour rated.

 

The door rating shall be adjusted to account for the two hour rated separation.