Clearance Sheet C2018-007681*002

 Department IssuesSigned OffIntl

Plans for a 16' CaptiveAire mode 5424 NP-2-BP-F kitchen hood.  Listed Clamped ducts will be utilized sealed with 3M fire barrier 2000 plus.  The plans are NOT APPROVED for the following reasons. 


                                                        
Reviewed using FFPC 6th edition effective Dec. 31, 2017.
Reviewer: PJ Webb 904 209 1744
 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

12/10/2020 agedris

RESUBMITTING: Please make necessary changes and resubmit the complete permit application package. Response to comments / plans / specifications should be submitted to the Permit Center as a resubmission for the original project unless other arrangements are made with the Fire Plan Reviewer or the Fire Plan Review Supervisor.

To help speed the review process you should include a written response to comments summary to clarify and/or illustrate corrections on plans (bubbling, highlighting, or notations are best). Please use the Florida Fire Prevention Code 6th Ed. for all code reference in a response to comments. You are required to remove old pages and reinsert the new pages.

The numbered items require a response or plans to be updated to complete the review.

12/10/2020 agedris

1) What is the wall behind the hood and the cooking equipment constructed of?  Demonstrate compliance with NFPA 96:4.2 or 4.2.3 all the way from the top of the hood to the floor. 

--------------

Hand written note provided indicating Metal Stud, 5/8 Fire Rock, 5/8 Durarock and stainless.  PJW Tuesday, November 24, 2020

11/24/2020 PWebb

2) Provide a roof plan view indicating the clearances to the items indicated in NFPA 96:7.8.2.1.

----------

Hand drawn sketch provided.  PJW Tuesday, November 24, 2020

11/24/2020 PWebb

3) The exhaust fan does not indicate that it is provided with a hinge, hold open retainer and flexible conduit.  NFPA 96:7.8.2.1, 8.1.2.1. 

-----------

Not provided, the CaptiveAire plans do not even indicate as an option.  PJW Tuesday, November 24, 2020

12/10/2020 agedris

4) How will you ensure that the cooking equipment will be returned to its original location?  Demonstrate compliance with NFPA 96:12.1.2.3.1. 

----------------

Not provided.  Cooking equipment specs not provided to determine if the equipment is wheeled or not.  PJW Tuesday, November 24, 2020

12/10/2020 agedris

5)  Provide an elevation view from the hood all the way to the exhaust fan.  Indicate any changes of direction, location of cleanouts, and clearance to combustibles.   If you are utilizing the double wall 0 clearance listed duct, indicate this and provide specs. 

--------------

Not provided.  Plans show a single wall strait duct run.   Provide plans and specs for the a double wall (0 clearance to combustibles) system, provide a plan showing that the clearance to combustibles is met, or indicate and provide specs for a listed product to reduce the clearances.  PJW Tuesday, November 24, 2020

12/10/2020 agedris

6) Provide manufacturers specifications for the cooking equipment.  NFPA 96:12.1.1

----------

Not Provided.  PJW Tuesday, November 24, 2020

12/10/2020 agedris

7) What is the roof pitch.  NFPA 96:7.8.2.2 requires access on all sides by a flat surface.   If the roof is not flat, provide details for the work platform. 

-------------

Not indicated.  PJW Tuesday, November 24, 2020

12/10/2020 agedris