SJC Home
Clearance Sheet C2018-007681*002

 Department IssuesSigned OffIntl

Plan reviewed for Interior build out of a restaurant. Reviewed using FFPC 6th edition effective Dec. 31, 2017.

Reviewer: 
Anthony Gedris 904-209-1741
 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

2/28/2020 agedris

RESUBMITTING:  Please make necessary changes and resubmit the complete permit application package. We do not accept responses to comments/ plans/ specifications through email. Contact Building department for resubmittals.

To help speed the review process you should include a written comment response summary to clarify or illustrate corrections on plans (bubbling, highlighting or notations are best).  Please use the Florida Fire Prevention Code 6th Ed for all code reference in a response to comments. The fire plans examiner does not use the Florida Building Code. You are required to remove old pages and reinsert the new pages.

The numbered items require a response or plans to be updated to complete the review.

2/28/2020 agedris

1) The emergency lights are required to provide 1-footcandle of illumination on the floor along the exit path. The E1 page does not provide adequate emergency lighting to cover the exit pathways for this space. Additional Lights are required. 101:7.9.2

***With my experience, a typical wall pack emergency light usually mounted 8' above the floor covers approx. 8' either direction with a 3' wide path.***

2-28-20 Spoke with Chris-571-0905 (Project Contact)He advised that additional emergency lighting would be added during construction to meet requirements. EM Lighting to be verified at final HOLD APPLIED AT FINAL - A.Gedris

 

2/28/2020 agedris

INFORMATIONAL ONLY NO RESPONSE NECESSARY:
The system(s) outlined in this set of plans is conceptual.

A HOLD has been placed at framing (105) until either: a) a permit has been pulled or b) a letter submitted from respective system contractor indicating no work to be done to the existing system:

- fire sprinkler system
- kitchen hood
- kitchen suppression system

2/28/2020 agedris