| | Department Issues | Signed Off | Intl |
|
|
#1
need energy sheets / per fec 405 lighting controls ; sensors required in all rooms including rest rooms
|
| |
|
|
#2
need signed sealed plan sheets where title block list architect
|
| |
|
|
#3
per fac signs are required to direct customers & visitors to interior spaces / rest rooms
|
| |
|
|
#4
per fac all rest rooms on an accessible route must be accessible
|
| |
|
|
#5
need accessibility detail sheet with all clearances , heights , reaches & turning radius
|
| |
|
|
#6
all exit access , path of travel & signs not shown
|
| |
|
|
#7
need walk in cooler drawings
|
| |
|
|
#8
need new ,existing outlets & lighting shown on electric plans
|
| |
|
|
#9
need load calculations & panel schedules on electric plans
|
| |
|
|
#10
need grease interceptor detail on plans with sizing calculated
|
| |
|
|
#11
need under slab grease line show on riser diagram
|
| |
|
|
#12
per fpc 802.1.1 each well of a multiple compartment sink shall discharge independently to a waste receptor [floor sink]indirect waste
|
| |