| | Department Issues | Signed Off | Intl |
|
|
Plan submitted for new 8' Captive Air exhaust system (fan, duct and hood). Reviewed using FFPC 7th edition effective January 1, 2021.
Reviewer: V.Vitori 904 209 1748
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
|
9/10/2021
| agedris |
|
|
RESUBMITTING: Please make necessary changes and resubmit the complete permit application package. Response to comments / plans / specifications should be submitted to the Permit Center as a resubmission for the original project unless other arrangements are made with the Fire Plan Reviewer or the Fire Plan Review Supervisor.
To help speed the review process you should include a written response to comments summary to clarify and/or illustrate corrections on plans (bubbling, highlighting, or notations are best). Please use the Florida Fire Prevention Code 7th Ed. for all code reference in a response to comments. You are required to remove old pages and reinsert the new pages.
The numbered items require a response or plans to be updated to complete the review.
|
9/10/2021
| agedris |
|
|
1) Distance to from duct to combustibles not illustrated or called out. Show/call out distances in accord with 96:4.4. 96:7.2 96:4.2.4.4
|
9/10/2021
| agedris |
|
|
2) Unsure of vertical duct cleaning access. How tall is roof? If over 10' how is safe access provided (ladder) ? 96:7.4.2.3
|
9/10/2021
| agedris |
|
|
3) Not provided illustration or information that shows compliance with 96:7.8.2.1(1), (2), (3), (8), (9).
|
9/10/2021
| agedris |
|
|
4) Do not see where upblast fan will be provided with hinge and supplied with flexible weatherproof electrical cable and service hold open retainers. 96:8.1.2
|
9/10/2021
| agedris |