Clearance Sheet C2018-007679*007

 Department IssuesSigned OffIntl

Plan reviewed for build out of 1300sf assembly in existing sprinklered building. Reviewed as new assembly using FFPC 7th edition effective January 1, 2021.

Reviewer: 
V.Vitori 904 209 1748

 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

Thursday, April 29, 2021 Resubmitted as a business occupancy. New review to be conducted. New comments will start with comment 6.

5/14/2021 VVitori

RESUBMITTING: Please make necessary changes and resubmit the complete permit application package. Response to comments / plans / specifications should be submitted to the Permit Center as a resubmission for the original project unless other arrangements are made with the Fire Plan Reviewer or the Fire Plan Review Supervisor.

To help speed the review process you should include a written response to comments summary to clarify and/or illustrate corrections on plans (bubbling, highlighting, or notations are best). Please use the Florida Fire Prevention Code 7th Ed. for all code reference in a response to comments. You are required to remove old pages and reinsert the new pages.

The numbered items require a response or plans to be updated to complete the review.

5/14/2021 VVitori

1) There are not 2 means of egress. There is only 1 exit. Provide 2nd exit. 101:12.2.4.1

Thursday, April 29, 2021 Occupancy now submitted as a business.

4/29/2021 VVitori

2) I am confused about fire walls separating adjacent spaces. Plan page A-1 shows walls on either side as 1hr separation with a handwritten strike through of 1hr and 2hr written in. Page A-2 shows wall detail for a 1 hour wall. Clearance sheet C2018-007679*006 was to add 1 hour separation walls for this unit. Clarify if the separation walls are remaining 1 hour or are being upgraded to 2 hour.

Response to comments indicates "The 1-hour wall (UL-419) not be upgraded. Refer to drawings sheet A-2 details 2. The building is also fully sprinklered."

4/29/2021 VVitori

3) You need to go back to Non DRC to revise site plan to include outdoor seating at front and vinyl fencing/walkin cooler at the rear.

Thursday, April 29, 2021 Response to comments indicate "The vinyl fencing/walkin cooler at the rear was removed from the project. The outdoor seating removed from project."

4/29/2021 VVitori

INFORMATIONAL ONLY NO RESPONSE NECESSARY:
The system(s) outlined in this set of plans is conceptual.

A HOLD has been placed at insulation inspection (109) until a permit has been pulled :

- Fire sprinkler system
- 200 gallon waste oil tank (see comment 5)
- Kitchen hood
- Kitchen suppression system

4/29/2021 VVitori

4) Will this space have 100+ lb CO2 tank on site? If so, demonstrate compliance with 55:13.10.

Thursday, April 29, 2021 Response to comments indicate "No CO2 tanks used on site."

4/29/2021 VVitori

5) Where will used cooking oil be stored? Will new cooking oil be stored on site? What is the quantity of each?  Show compliance with 1:66.19.7.

Thursday, April 29, 2021 Response to comments indicate "(1) 35 lbs box cooking oil (4.5 gals) capacity stored on site in fryers. The used/waste oil are stored in a metal container (200 gallons capacity) located at the back of the site away from the building."

A hold at 109 framing for an above ground waste oil tank permit will be required.

4/29/2021 VVitori

6) This was resubmitted as a business. A restaurant with an occupant load less than 50 is a mercantile. See annex 101:3.3.196.9 and 101:6.1.10.1 for clarification.

NOTE:

a)New review of new submittal of business stopped where this does not meet business occupancy.

b) Off hand, a mercantile will allow a 1 hour separation in a sprinklered building IF all control valves on sprinkler are supervised. When I spoke with Mr. Surage on 4 7 21 at 433 via phone, documentation from fire alarm or sprinkler contractor is to be provided which indicates that all sprinkler valves (including backflow) is electronically supervised.

Thursday, May 6, 2021 Plans resubmitted as mercantile. Walls separating tenant spaces are 1 hr. Note says "sprinkler contractor to provide documentation to indicate that all sprinkler control values are supervised per current code."   This documentation needs to be provided now because if the valves are not electronically supervised then a decision needs to be made. I then would need to know if the wall will be 2 hour or the tenant intends to electronically supervise all valves.

Friday, May 14, 2021 Plans resubmitted and still show mercantile with a 2 hour separation to adjacent assembly and 1 hour separation to vacant space.

5/14/2021 VVitori

7) Newly provided pages were not inserted in to existing plan set while old pages were removed. Newly provided pages need to be swapped out with the old.

5/6/2021 VVitori