Plan reviewed for build out of 1300sf assembly in existing sprinklered building. Reviewed as new assembly using FFPC 7th edition effective January 1, 2021.
Reviewer: V.Vitori 904 209 1748
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
Thursday, April 29, 2021 Resubmitted as a business occupancy. New review to be conducted. New comments will start with comment 6.
|
| |
|
|
RESUBMITTING: Please make necessary changes and resubmit the complete permit application package. Response to comments / plans / specifications should be submitted to the Permit Center as a resubmission for the original project unless other arrangements are made with the Fire Plan Reviewer or the Fire Plan Review Supervisor.
To help speed the review process you should include a written response to comments summary to clarify and/or illustrate corrections on plans (bubbling, highlighting, or notations are best). Please use the Florida Fire Prevention Code 7th Ed. for all code reference in a response to comments. You are required to remove old pages and reinsert the new pages.
The numbered items require a response or plans to be updated to complete the review.
|
| |
|
|
1) There are not 2 means of egress. There is only 1 exit. Provide 2nd exit. 101:12.2.4.1
Thursday, April 29, 2021 Occupancy now submitted as a business.
|
4/29/2021
| VVitori |
|
|
2) I am confused about fire walls separating adjacent spaces. Plan page A-1 shows walls on either side as 1hr separation with a handwritten strike through of 1hr and 2hr written in. Page A-2 shows wall detail for a 1 hour wall. Clearance sheet C2018-007679*006 was to add 1 hour separation walls for this unit. Clarify if the separation walls are remaining 1 hour or are being upgraded to 2 hour.
Response to comments indicates "The 1-hour wall (UL-419) not be upgraded. Refer to drawings sheet A-2 details 2. The building is also fully sprinklered."
|
4/29/2021
| VVitori |
|
|
3) You need to go back to Non DRC to revise site plan to include outdoor seating at front and vinyl fencing/walkin cooler at the rear.
Thursday, April 29, 2021 Response to comments indicate "The vinyl fencing/walkin cooler at the rear was removed from the project. The outdoor seating removed from project."
|
4/29/2021
| VVitori |
|
|
INFORMATIONAL ONLY NO RESPONSE NECESSARY: The system(s) outlined in this set of plans is conceptual.
A HOLD has been placed at insulation inspection (109) until a permit has been pulled :
- Fire sprinkler system - 200 gallon waste oil tank (see comment 5) - Kitchen hood - Kitchen suppression system
|
4/29/2021
| VVitori |
|
|
4) Will this space have 100+ lb CO2 tank on site? If so, demonstrate compliance with 55:13.10.
Thursday, April 29, 2021 Response to comments indicate "No CO2 tanks used on site."
|
4/29/2021
| VVitori |
|
|
5) Where will used cooking oil be stored? Will new cooking oil be stored on site? What is the quantity of each? Show compliance with 1:66.19.7.
Thursday, April 29, 2021 Response to comments indicate "(1) 35 lbs box cooking oil (4.5 gals) capacity stored on site in fryers. The used/waste oil are stored in a metal container (200 gallons capacity) located at the back of the site away from the building."
A hold at 109 framing for an above ground waste oil tank permit will be required.
|
4/29/2021
| VVitori |
|
|
6) This was resubmitted as a business. A restaurant with an occupant load less than 50 is a mercantile. See annex 101:3.3.196.9 and 101:6.1.10.1 for clarification.
NOTE:
a)New review of new submittal of business stopped where this does not meet business occupancy.
b) Off hand, a mercantile will allow a 1 hour separation in a sprinklered building IF all control valves on sprinkler are supervised. When I spoke with Mr. Surage on 4 7 21 at 433 via phone, documentation from fire alarm or sprinkler contractor is to be provided which indicates that all sprinkler valves (including backflow) is electronically supervised.
|
| |
|
|
7) Newly provided pages were not inserted in to existing plan set while old pages were removed. Newly provided pages need to be swapped out with the old.
|
| |