Plan reviewed for revision to 2 - type I exhaust hoods (9' hood and 10' hood adjacent to each other) by a completely new designer. The hoods we be reviewed as new since I don't know what has changed and this is a new plan page. Reviewed using FFPC 6th edition effective Dec. 31, 2017.
Reviewer:
V.Vitori 904 209 1748
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
Also submitted was new suppression system page showing Range Guard suppression vs the already approved Ansul. Have suppression contractor submit revision to his plans. 10 28 20 Supervisor said go ahead and review suppression.