SJC Home
Clearance Sheet C2018-007679*005

 Department IssuesSigned OffIntl

Plan reviewed for revision to 2 - type I exhaust hoods (9' hood and 10' hood adjacent to each other) by a completely new designer.  The hoods we be reviewed as new since I don't know what has changed and this is a new plan page.  Reviewed using FFPC 6th edition effective Dec. 31, 2017.

Reviewer: 
V.Vitori 904 209 1748

 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

Also submitted was new suppression system page showing Range Guard suppression vs the already approved Ansul. Have suppression contractor submit revision to his plans.

 

1) Plan page KH-1 indicates "16 ga. galv steel" will be used. 96:7.5.1 allows 16 ga carbon steel or 18ga stainless steel.

 

RESUBMITTING: Please make necessary changes and resubmit the complete permit application package. Response to comments / plans / specifications should be submitted to the Permit Center as a resubmission for the original project unless other arrangements are made with the Fire Plan Reviewer or the Fire Plan Review Supervisor.

To help speed the review process you should include a written response to comments summary to clarify and/or illustrate corrections on plans (bubbling, highlighting, or notations are best). Please use the Florida Fire Prevention Code 6th Ed. for all code reference in a response to comments. You are required to remove old pages and reinsert the new pages.

The numbered items require a response or plans to be updated to complete the review.