Plan reviewed for

Reviewed using FFPC 6th edition effective Dec. 31, 2017. NFPA 1 and 101 references are Florida Editions of the code in the FFPC.

Plans is

Reviewer: D. Feagle 904-209-1721

To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

8/10/2020 dfeagle

RESUBMITTING: Please make necessary changes and resubmit the complete permit application package. Response to comments / plans / specifications should be submitted to the Permit Center as a resubmission for the original project unless other arrangements are made with the Fire Plan Reviewer or the Fire Plan Review Supervisor.

To help speed the review process you should include a written response to comments summary to clarify and/or illustrate corrections on plans (bubbling, highlighting, or notations are best). Please use the Florida Fire Prevention Code 6th Ed. for all code reference in a response to comments. You are required to remove old pages and reinsert the new pages.

The numbered items require a response or plans to be updated to complete the review.

8/10/2020 dfeagle

NFPA 13 9.2.1.3.3.2  Provide spec sheet for suspended ceiling tile grid showing it meets ASTM C 635.

NFPA 13 9.2.1.3.3.4 *   Where flexible sprinkler hose fittings are used to connect sprinklers to branch lines in suspended ceilings, a label limiting relocation of the sprinkler shall be provided on the anchoring component.
An example of language for the label is as follows: CAUTION: DO NOT REMOVE THIS LABEL.Relocation of this device should only be performed by qualified and/or licensed individuals that are aware of the original system design criteria, hydraulic criteria, sprinkler head listing parameters, and knowledge of the state and local codes including NFPA 13 installation standards. Relocation of the device without this knowledge could adversely affect the performance of this fire protection and life safety system.

Friday, August 7, 2020 1439 hrs. DF: I spoke with Brad Bell with DynaFire regarding the ceiling grid spec sheet. Brad said he will verify with me and if it is ASTM C 1635, email the spec sheet. I also emailed Brad the code reference and said that I will hold the rejecting the permit until COB Monday 08/10/20.

Monday, August 10, 2020 1200 hrs. DF: Received via email from Mr. Bell a copy of USG DONN Brand DX/DXL Acoustical Suspension System meeting ASTM C 635.

8/10/2020 dfeagle