Plan submitted for revision to several 11 or 18 pages(depending on which set one looks at). Reviewed using FFPC 7th edition effective January 1, 2021. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code. Reviewer: V.Vitori For questions regarding comments you may reach me at either: 904 209 1748 or vvitori@sjcfl.us. To schedule fire inspections call 827 6842 (automated system). Questions about inspections or resubmitting your plans call 209 1740x1.
RESUBMITTING:A. Make necessary changes and resubmit everything in person to the Permit Center. B. Once at the Permit Center swap out altered pages in EACH plan set (job and office). One copy of the removed/old pages will need to be resubmitted and labeled "OLD". Do not forget to remove pages for work not associated in this permit.C. Provide a response to comments along with any supporting documentation. Response to comments is REQUIRED not optional. - The response to comments sheet will need to include a response to each numbered comment and tell us where in the plans the comment was addressed. Ex - "top left of page A11" or "Page E1 note 8". - Code responses shall reference Florida Fire Prevention Code 7th Ed. (not Building Code)
1) There are not 2 complete matching sets of plans. Provide 2 complete matching sets of plans.
Set 1 has: G2, A1, A1.2, A1.3, A3.1, P1, P2, P3, E3, E4, E5
Set 2 has: G2, A1, A1.2, A1.3, A3.1, P1, P2, P3, P4, P5, P6, P7, M2, M3, M4, E3, E4, E5.