Plan reviewed for a Five Below build out sprinkler system in a 8,204 Sq. Ft mercantile building in a construction type IIB fire sprinklered building. There will be 3 units 1 hour separated. . Reviewed using FFPC 6th edition effective Dec. 31, 2017.
Reviewer: Joseph Branton 904-209-1721 To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
|
2/6/2019
| jbranton |
|
|
RESUBMITTING: Please make necessary changes and resubmit the complete permit application package. We do not accept responses to comments/ plans/ specifications through email. Contact Building department for resubmittals.
To help speed the review process you should include a written comment response summary to clarify or illustrate corrections on plans (bubbling, highlighting or notations are best). Please use the Florida Fire Prevention Code 6th Ed for all code reference in a response to comments. The fire plans examiner does not use the Florida Building Code. You are required to remove old pages and reinsert the new pages.
The numbered items require a response or plans to be updated to complete the review.
|
2/6/2019
| jbranton |
|
|
1.) An ENGINEERED sealed Design Criteria for a fire sprinkler system exceeding 49 heads is required to be submitted with the general construction documents. We are unable to approve the plan until this information is provided. (FAC 61G15-32.002(5)) (The signed and sealed design criteria is the general guidelines with design and scope of the sprinkler system. It is not a full set of shop drawing.) THIS IS WHAT IS REQUIRED BY FLORIDA ADMINISTRATIVE CODE 61G15-32.004, (A-M) as of June 19th, 2015, Design of Water Based Fire Protection Systems.
Waiting for updated design criteria. build out Hazard areas are different from shell.
|
3/14/2019
| jbranton |
|
|
Do not forget to:
- include hydraulic design information sign AND general information sign at riser. NFPA 13 Ch24.
- ID control, drain, and test connection valves with a weatherproof metal or rigid plastic sign. NFPA 13 6.7.4
- include a stock of spare sprinklers in a cabinet on premises in an area not to exceed 100 degrees WITH a wrench for each type of sprinkler installed or to be used. NFPA 13 6.2.9
- a list of the sprinklers installed in the property shall be posted in the sprinkler cabinet. It shall include: 1) SIN or manufacturer, model, orifice, deflector type, thermal sensitivity, and pressure rating 2) general description 3) quantity of each type to be contained in cabinet 4) Issue or revision date of list. NFPA 13 6.2.9.7
|
2/6/2019
| jbranton |
|
|
2.) Sheet 1 of 1 riser supply does not match approved underground. Correct drawings
Corrected to show a 6" going to riser. 3/14/19 JSB
|
3/14/2019
| jbranton |