SJC Home
Clearance Sheet C2018-005320*004

 Department IssuesSigned OffIntl

Plan reviewed for 38 device expansion to existing fire alarm system. They are tieing this suites devices into existing shell alarm.  Reviewed using FFPC 7th edition effective January 1, 2021.

Reviewer: 
V.Vitori 904 209 1748

 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

 

According to page E2.1 there will be standard illumination motion sensors. Make sure they are tied in at final. Once the fire alarm is in alarm the standard illumination in the path of egress must illuminate.

3/24/2021 VVitori