Plan reviewed for build out of a 6082sf new business. Reviewed as new business using FFPC 6th edition effective Dec. 31, 2017.

Reviewer: 
V.Vitori 904 209 1748

 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

1/16/2020 VVitori

INFORMATIONAL ONLY NO RESPONSE NECESSARY:
The system(s) outlined in this set of plans is conceptual.

A HOLD has been placed at framing (105) until either: a) a permit has been pulled or b) a letter submitted from respective system contractor indicating no work to be done to the existing system:
- fire sprinkler system

1/16/2020 VVitori

Page E2.1 indicates that motion sensors will be used in the areas of egress. At time of fire final be prepared to show compliance with NFPA 101 7.8.1.2.2:

(1) switch controllers must be listed (2) switch controllers equipped for fail-safe operation and evaluated for this purpose (3)  timers be set for a minimum 15 minute duration. (4)  motion sensor be activated by any occupant movement in the area served by lighting units (5) If building has a fire alarm, activation of fire alarm must activate the switch controller (6)  lighting control device may not turn off any lights realized upon for activation of photo luminescent exit signs or path markers (7) Lighting control devices may not turn off any battery equipped emergency luminaries, unit equipment or exit signs.

1/16/2020 VVitori

Page 601 shows door 101 is going to receive passage hardware. Page E1.1 shows that door 101 is going to be prewired for "pull string door strike". If the intent is going to be to add electronically controlled egress, access controlled egress or delayed egress later on, either:

a) this permit will need to be modified to show compliance with the respective code prior to final OR

b) a separate permit will need to be pulled showing compliance with the respective code if work is done following the final of this permit.

1/16/2020 VVitori

At the time of fire final be prepared to provide a copy of the manufacturer specification sheets to the fire inspector showing that each interior finish will meet:

- wall and ceiling finish will meet Class A, B or C. 101:38.3.3.2.2

- floor finish shall meet either: a) ASTM D 2859 for carpet and carpet like materials or b) has a minimum critical radiant flux of .1 W/cm2 for non carpet flooring. 101:38.3.3.3.3.

If there are multiple finishes, label each spec sheet identifying each product, its location AND highlight the area showing illustrating it meets the applicable Code requirement.

1/16/2020 VVitori