| | Department Issues | Signed Off | Intl |
|
|
Plan reviewed for 7379sf business (2979sf) and Storage (4400sf). Reviewed using FFPC 6th edition effective Dec. 31, 2017. Reviewer: Sandra Boike 904 209 1741 Victoria Vitori 904 209 1748 To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
Wednesday, July 11, 2018
Letter from architect stating the fire alarm is not required and all notations for the fire alarm have been removed. Reviewer still found notes on plans for FA.
|
6/15/2018
| sboike |
|
|
RESUBMITTING: Please make necessary changes and resubmit the complete permit application package.
To help speed the review process you should include a written comment response summary to clarify or illustrate corrections on plans (bubbling, highlighting or notations are best). Please use the Florida Fire Prevention Code 6th Ed for all code reference in a response to comments. The fire plans examiner does not use the Florida Building Code. You are required to remove old pages and reinsert the new pages.
The numbered items require a response or plans to be updated to complete the review. Items labled "informational only" are for the contractor.
|
7/11/2018
| sboike |
|
|
1) A601 has door used in the fire separation of business occupancy and the industrial. This door has a note stating the "Hold open device sill be tied into the fire alarm" There is not other notation of a fire alarm for the building. A comments has been added for the fire alarm engineering criteria.
Wednesday, July 11, 2018
Page A002, E102, E201 still indicates fir alarm in fire protection notes.
Wednesday, July 25, 2018
Notes have been removed.
|
7/25/2018
| sboike |
|
|
2) An ENGINEERED signed and sealed Design Criteria for the fire alarm system over $5000.00 is required to be submitted with the general construction documents. FAC 61G15-32.002(5) We are unable to approve the plan until this information is provided. (The Design Criteria is not a full set of shop drawings.) THIS IS WHAT IS REQUIRED BY FLORIDA ADMINISTRATIVE CODE 61G15-32.008,(A-O) Design of Fire Alarms and Detection Systems.
Wednesday, July 25, 2018
Reference to FA and FS have been removed.
|
7/25/2018
| sboike |