| | Department Issues | Signed Off | Intl |
|
|
Plan reviewed for new 11 device addressable fire alarm system to monitor water flow and has 3 duct detectors in suite E106 tied in and will be monitored with 2 phone lines. Reviewed using FFPC 6th edition effective Dec. 31, 2017. Reviewer: Sandra Boike 904 209 1741 Victoria Vitori 904 209 1748 To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
|
| |
|
|
1) No fire alarm device functions illustrated showing which devices activate particular fire alarm output functions. 101:9.6.3.2.2
NOTE: Make sure that the duct detectors only activate a supervisory signal as opposed to alarm signal.
|
| |
|
|
2)Looking at original construction plans it does not appear that the FACP will be in a climate controlled room. Please address. 72:10.3.5
|
| |
|
|
RESUBMITTING: Please make necessary changes and resubmit the complete permit application package. We do not accept responses to comments/ plans/ specifications through email. Contact Building department for resubmittals.
To help speed the review process you should include a written comment response summary to clarify or illustrate corrections on plans (bubbling, highlighting or notations are best). Please use the Florida Fire Prevention Code 6th Ed for all code reference in a response to comments. The fire plans examiner does not use the Florida Building Code. You are required to remove old pages and reinsert the new pages.
The numbered items require a response or plans to be updated to complete the review. Items labled "informational only" a
|
| |