Plan reviewed for SHELL only 11060 sf sprinklered and FA monitor. Reviewed using FFPC 6th edition effective Dec. 31, 2017. Reviewer: Sandra Boike 904 209 1741 Victoria Vitori 904 209 1748 To schedule fire inspections please call 209-1740x1 then 1 again. To leave a message extension 1 then 2. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
Monday, May 14, 2018
Letter submitted by Bloc 3 Design dated 5/7/2018. Responses to comments provided below.
|
3/27/2018
| sboike |
|
|
RESUBMITTING: Please make necessary changes and resubmit the complete permit application package.
To help speed the review process you should include a written comment response summary to clarify or illustrate corrections on plans (bubbling, highlighting or notations are best). Please use the Florida Fire Prevention Code 6th Ed for all code reference in a response to comments. The fire plans examiner does not use the Florida Building Code. You are required to remove old pages and reinsert the new pages.
The numbered items require a response or plans to be updated to complete the review. Items labled "informational only" are for the contractor.
|
3/27/2018
| sboike |
|
|
1) An ENGINEERED sealed Design Criteria for a fire sprinkler system exceeding 49 heads is required to be submitted with the general construction documents. We are unable to approve the plan until this information is provided. (FAC 61G15-32.002(5)) (The signed and sealed design criteria is the general guidelines with design and scope of the sprinkler system. It is not a full set of shop drawing.) THIS IS WHAT IS REQUIRED BY FLORIDA ADMINISTRATIVE CODE 61G15-32.004, (A-M) as of June 19th, 2015, Design of Water Based Fire Protection Systems.
Monday, May 14, 2018
Response: Fire sprinkler engineering will be submitted as shop drawings.
Friday, May 25, 2018
EOR is R Hinkle, Item (i) has "Jacksonville Fire Rescue". Is this design criteria for this building? If this is the correct design criteria please remove the reference to Jacksonville Fire Rescue. There is also, one item missing for the maxium allowable pressure drop. Please indicate in the design criteria what is acceptable pressure drop and resubmit.
|
| |
|
|
2) Exit signs must match BOTH Electrical page(s) and Life Safety Code page(s).
Monday, May 14, 2018
Response: Plan pages have been updated.
|
5/14/2018
| sboike |
|
|
3) An ENGINEERED signed and sealed Design Criteria for the fire alarm system over $5000.00 is required to be submitted with the general construction documents. FAC 61G15-32.002(5) We are unable to approve the plan until this information is provided. (The Design Criteria is not a full set of shop drawings.) THIS IS WHAT IS REQUIRED BY FLORIDA ADMINISTRATIVE CODE 61G15-32.008,(A-O) Design of Fire Alarms and Detection Systems.
Monday, May 14, 2018
Response: Fire alarm engineering drawings will be submitted as shop drawings.
Comment: Please see the requirement below. (If the fire alarm valuation is less than $5,000 then submit quote.)
Engineering criteria for fire alarm systems and fire protection systems are required to be submitted in the General construction documents. Per Florida Administrative Code (FAC) 61G15-2.0029(5)"Fire Protection System Engineering Documents: The fire protection system engineering drawings, specifications, prescriptive and performance criteria, water supply analysis and other materials or representations, which are submitted with the general construction documents pursuant to Section 553.79(6),"
Friday, May 25, 2018
Letter from life safety states the fire alarm system will be less than $5,000.
|
5/25/2018
| sboike |
|
|
4) Do Not resubmit until you have obtained a clearance sheet.
|
5/14/2018
| sboike |