SJC Home
Clearance Sheet C2018-002140

 Department IssuesSigned OffIntl

Plan reviewed for 13,000sf retail space. Reviewed using FFPC 6th edition effective Dec. 31, 2017.
Reviewer: Sandra Boike 904 209 1741 
Victoria Vitori 904 209 1748
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

Monday, May 14, 2018

Response to comment letter submitted 5/7/2018 from Bloc 3 Design.

5/14/2018 sboike

RESUBMITTING:
Please make necessary changes and resubmit the complete permit application package.

To help speed the review process you should include a written comment response summary to clarify or illustrate corrections on plans (bubbling, highlighting or notations are best).  Please use the Florida Fire Prevention Code 6th Ed for all code reference in a response to comments. The fire plans examiner does not use the Florida Building Code. You are required to remove old pages and reinsert the new pages.

The numbered items require a response or plans to be updated to complete the review. Items labled "informational only" are for the contractor.

5/14/2018 sboike

An ENGINEERED sealed Design Criteria for a fire sprinkler system exceeding 49 heads is required to be submitted with the general construction documents. We are unable to approve the plan until this information is provided. (FAC 61G15-32.002(5)) (The signed and sealed design criteria is the general guidelines with design and scope of the sprinkler system. It is not a full set of shop drawing.) THIS IS WHAT IS REQUIRED BY FLORIDA ADMINISTRATIVE CODE 61G15-32.004, (A-M) as of June 19th, 2015, Design of Water Based Fire Protection Systems.

Monday, May 14, 2018

Response: Fire sprinkler engineering drawings will be submitted as a shop drawing.

Comment: Please see the state requirement below.

Friday, May 25, 2018

EOR is R Hinkle, Item (i) has "Jacksonville Fire Rescue". Is this design criteria for this building? If this is the correct design criteria please remove the reference to Jacksonville Fire Rescue.  There is also, one item missing for the maxium allowable pressure drop. Please indicate in the design criteria what is acceptable pressure drop and resubmit.

 

 

 

An ENGINEERED signed and sealed Design Criteria for the fire alarm system over $5000.00 is required to be submitted with the general construction documents. FAC 61G15-32.002(5) We are unable to approve the plan until this information is provided. (The Design Criteria is not a full set of shop drawings.) THIS IS WHAT IS REQUIRED BY FLORIDA ADMINISTRATIVE CODE 61G15-32.008,(A-O) Design of Fire Alarms and Detection Systems.

Monday, May 14, 2018

Monday, May 14, 2018

Response: Fire alarm engineering drawings will be submitted as a shop drawing.

Comment: Please see the state requirement below.

Engineering criteria for fire alarm systems and fire protection systems are required to be submitted in the General construction documents. Per Florida Administrative Code (FAC) 61G15-2.0029(5)"Fire Protection System Engineering Documents: The fire protection system engineering drawings, specifications, prescriptive and performance criteria, water supply analysis and other materials or representations, which are submitted with the general construction documents pursuant to Section 553.79(6),"

Friday, May 25, 2018

Letter submitted by life safety stating the fire alarm system is under $5,000.

5/25/2018 sboike