Page A611 shows several interior floor finishes. Several of the listed floor finishes show they meet class A or C. Floor finishes are required to meet usually Class I, II, ASTM D 2859 or have a minimum critical radiant flux.
For this project, the contractor will need to provide the fire inspector at time of final a copy of manufacturer spec sheets of floor finish products used showing they all meet either: a) ASTM D 2859 for carpet and carpet like materials or b) has a minimum critical radiant flux of .1 W/cm2 for non carpet flooring. 101:36.3.3.3.
Since there are multiple finishes, please label each spec sheet identifying each product, its location AND highlight the area showing illustrating it meets the applicable Code requirement.