Plan reviewed for build out of new 4004sf mercantile in an existing construction type IIB sprinklered building. This unit is separated from its neighbor by a 1 hour rated wall assembly. Reviewed as new mercantile class C using FFPC 6th edition effective Dec. 31, 2017.

Reviewer: 
Anthony Gedris 904-209-1741
Victoria Vitori 904 209 1748
 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

3/12/2019 VVitori

Page A611 shows several interior floor finishes. Several of the listed floor finishes show they meet class A or C. Floor finishes are required to meet usually Class I, II, ASTM D 2859 or have a minimum critical radiant flux.

For this project, the contractor will need to provide the fire inspector at time of final a copy of manufacturer spec sheets of floor finish products used showing they all meet either: a) ASTM D 2859 for carpet and carpet like materials or b) has a minimum critical radiant flux of .1 W/cm2 for non carpet flooring. 101:36.3.3.3.

Since there are multiple finishes, please label each spec sheet identifying each product, its location AND highlight the area showing illustrating it meets the applicable Code requirement.

3/12/2019 VVitori

Looking at page E2, there are several locations with occupancy sensors. Make sure occupancy illumination timers are provided and set for a minimum 15-minute duration. Also make sure that lighting control device does not turn off any battery-equipped emergency luminaires, unit equipment or exit signs. 101:7.8.1.2.2

3/12/2019 VVitori

INFORMATIONAL ONLY NO RESPONSE NECESSARY:
The system(s) outlined in this set of plans is conceptual.

A HOLD has been placed at framing (105) until either: a) a permit has been pulled or b) a letter submitted from respective system contractor indicating no work to be done to the existing system:
- fire sprinkler system

3/12/2019 VVitori