SJC Home
Clearance Sheet C2018-002137

 Department IssuesSigned OffIntl

Plan reviewed for new 7 device addressable fire alarm system to monitor water flow and has 1 duct detector in suite G107 tied in and will be monitored with 2 phone lines. Reviewed using FFPC 6th edition effective Dec. 31, 2017.
Reviewer: Sandra Boike 904 209 1741 
Victoria Vitori 904 209 1748
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

Friday, September 28, 2018 Hand written response to comments has been provided on copy of plan review comments.

9/28/2018 sboike

1) No fire alarm device functions illustrated showing which devices activate particular fire alarm output functions.  101:9.6.3.2.2

NOTE: Make sure that the duct detectors only activate a supervisory signal as opposed to alarm signal.

Friday, September 28, 2018- Matrix has been provided on the plan.

9/28/2018 sboike

2)Looking at original construction plans it does not appear that the FACP will be in a climate controlled room. Please address. 72:10.3.5

Friday, September 28, 2018- Response indicates new equipment has been provided. 6700 Honeywell Silent Knight panel.

9/28/2018 sboike

RESUBMITTING:  Please make necessary changes and resubmit the complete permit application package. We do not accept responses to comments/ plans/ specifications through email. Contact Building department for resubmittals.

To help speed the review process you should include a written comment response summary to clarify or illustrate corrections on plans (bubbling, highlighting or notations are best).  Please use the Florida Fire Prevention Code 6th Ed for all code reference in a response to comments. The fire plans examiner does not use the Florida Building Code. You are required to remove old pages and reinsert the new pages.

The numbered items require a response or plans to be updated to complete the review. Items labled "informational only" a

9/28/2018 sboike