| | Department Issues | Signed Off | Intl |
|
|
Plan reviewed for 3000sf mercantile. Reviewed using FFPC 6th edition effective Dec. 31, 2017. Reviewer: Sandra Boike 904 209 1741 Victoria Vitori 904 209 1748 To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
|
5/17/2018
| sboike |
|
|
RESUBMITTING: Please make necessary changes and resubmit the complete permit application package.
To help speed the review process you should include a written comment response summary to clarify or illustrate corrections on plans (bubbling, highlighting or notations are best). Please use the Florida Fire Prevention Code 6th Ed for all code reference in a response to comments. The fire plans examiner does not use the Florida Building Code. You are required to remove old pages and reinsert the new pages.
The numbered items require a response or plans to be updated to complete the review. Items labled "informational only" are for the contractor.
|
5/17/2018
| sboike |
|
|
1) An ENGINEERED signed and sealed Design Criteria for the fire alarm system over $5000.00 is required to be submitted with the general construction documents. FAC 61G15-32.002(5) We are unable to approve the plan until this information is provided. (The Design Criteria is not a full set of shop drawings.) THIS IS WHAT IS REQUIRED BY FLORIDA ADMINISTRATIVE CODE 61G15-32.008,(A-O) Design of Fire Alarms and Detection Systems.
Thursday, May 17, 2018
Design criteria not provided this submittal.
Engineering criteria for fire alarm systems and fire protection systems are required to be submitted in the General construction documents. Per Florida Administrative Code (FAC) 61G15-2.0029(5)"Fire Protection System Engineering Documents: The fire protection system engineering drawings, specifications, prescriptive and performance criteria, water supply analysis and other materials or representations, which are submitted with the general construction documents pursuant to Section 553.79(6),"
|
| |
|
|
2) An ENGINEERED sealed Design Criteria for a fire sprinkler system exceeding 49 heads is required to be submitted with the general construction documents. We are unable to approve the plan until this information is provided. (FAC 61G15-32.002(5)) (The signed and sealed design criteria is the general guidelines with design and scope of the sprinkler system. It is not a full set of shop drawing.) THIS IS WHAT IS REQUIRED BY FLORIDA ADMINISTRATIVE CODE 61G15-32.004, (A-M) as of June 19th, 2015, Design of Water Based Fire Protection Systems.
Thursday, May 17, 2018
Design criteria not provided this submittal.
Engineering criteria for fire alarm systems and fire protection systems are required to be submitted in the General construction documents. Per Florida Administrative Code (FAC) 61G15-2.0029(5)"Fire Protection System Engineering Documents: The fire protection system engineering drawings, specifications, prescriptive and performance criteria, water supply analysis and other materials or representations, which are submitted with the general construction documents pursuant to Section 553.79(6),"
|
| |
|
|
INFORMATIONAL ONLY NO RESPONSE NECESSARY: The system(s) outlined in this set of plans is conceptual.
A HOLD has been placed at framing (105) until either: a) a permit has been pulled or b) a letter submitted from respective system contractor indicating no work to be done to the existing system: - fire alarm system - fire sprinkler system - fire underground - fire department access box (Fail Safe)
|
5/17/2018
| sboike |
|
|
3) No information has been indicated on the plan for a fixture or display. Is this a shell?
Thursday, May 17, 2018
Plans reviewed as shell.
|
5/17/2018
| sboike |
|
|
4) What is the hazard classification as required by 36.1.5.1 The contents of mercantile occupancies shall be classified in accordance with Section 6.2. Provide classification on plan.
Thursday, May 17, 2018
OH
|
5/17/2018
| sboike |