SJC Home
Clearance Sheet C2018-002137*003

 Department IssuesSigned OffIntl

Plan reviewed for 1500sf modification of existing space in an existing fire sprinklered building. Scope of work only covers adding a single restroom, temporary lighting, hvac unit.  Reviewed as new class c mercantile using FFPC 6th edition effective Dec. 31, 2017.

Reviewer: 
Victoria Vitori 904 209 1748

 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

NOTE: I do not currently do not see a tenant build out on either side of this unit. Only see a Smoothie King in suite 107.

Wednesday, December 11, 2019  Restamp

11/18/2019 VVitori

At the time of fire final be prepared to provide a copy of manufacturer specification sheets to the fire inspector showing that each interior finish will meet:

- wall and ceiling will meet Class A, B or C. 101:36.3.3.2

- floor finish will meet either: a) ASTM D 2859 for carpet and carpet like materials or b) has a minimum critical radiant flux of .1 W/cm2 for non carpet flooring. 101:36.3.3.3.3.

If there are multiple finishes, label each spec sheet identifying each product, its location AND highlight the area showing illustrating it meets the applicable Code requirement.

11/18/2019 VVitori
INFORMATIONAL ONLY NO RESPONSE NECESSARY:
Air handlers with more than 2000 CFM are required to have duct smoke detectors. If these detectors are concealed they shall have a remote visual and audible indicators located in a normally occupied space. (NOTE if there is a FIRE ALARM SYSTEM in the building the duct smoke detector must also be connected to the fire alarm system. In those cases only a visual indicator is required) (NFPA 90A,6.4.2)
11/18/2019 VVitori

INFORMATIONAL ONLY NO RESPONSE NECESSARY:
The system(s) outlined in this set of plans is conceptual.

A HOLD has been placed at framing (105) until either: a) a permit has been pulled or b) a letter submitted from respective system contractor indicating no work to be done to the existing system:
- fire alarm system
- fire sprinkler system

11/18/2019 VVitori