At the time of fire final be prepared to provide a copy of manufacturer specification sheets to the fire inspector showing that each interior finish will meet:
- wall and ceiling will meet Class A, B or C. 101:36.3.3.2
- floor finish will meet either: a) ASTM D 2859 for carpet and carpet like materials or b) has a minimum critical radiant flux of .1 W/cm2 for non carpet flooring. 101:36.3.3.3.3.
If there are multiple finishes, label each spec sheet identifying each product, its location AND highlight the area showing illustrating it meets the applicable Code requirement.