SJC Home
Clearance Sheet C2018-001792

 Department IssuesSigned OffIntl

Plan reviewed for. Reviewed using FFPC 6th edition effective Dec. 31, 2017.

Reviewer: 
Joseph Branton 904-209-1721
 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

4/16/2019 jbranton

RESUBMITTING:  Please make necessary changes and resubmit the complete permit application package. We do not accept responses to comments/ plans/ specifications through email. Contact Building department for resubmittals.

To help speed the review process you should include a written comment response summary to clarify or illustrate corrections on plans (bubbling, highlighting or notations are best).  Please use the Florida Fire Prevention Code 6th Ed for all code reference in a response to comments. The fire plans examiner does not use the Florida Building Code. You are required to remove old pages and reinsert the new pages.

The numbered items require a response or plans to be updated to complete the review.

4/16/2019 jbranton

1.) Page FP3 box 61g15-32.003(4) indicates that the fire protection contractor will need to get their engineer to sign and seal the shop drawings. Per FAC 61G15-32.002(5)(6) after the Fire protection system engineering documents (Criteria) is submitted with the building plans, the shop drawings, when submitted, require no additional engineering input or seal.

Please either: 1) Remove this comment or 2)clarify the comment preparing the fire sprinkler contractor to provide: a) Have ___new engineer____ submit a registered letter to ___EOR____ notifying to reuse the already sealed contract documents therefore assuming all legal responsibility for the system in accordance with FAC 61G15-27.001. or 3) Have the owner or project engineer submit a letter to our office completely removing ___EOR____ as engineer of record for the project. or 4) Have the engineer of record provide a note on the shop plans they approve for design requirements and performance only.

The above comment is in reference to the EOR stating he must approve contractor drawings as stated in the original 61g15-32.003 and 61g15-32.004 (comments #4 on both).  You submitted shop drawings signed and sealed by your own Engineer.  You can not have 2 engineer of records on one job.  Correct and resubmit. Coordinate with John Buchanan,the original EOR.  JSB 4/16/19 

Plans resubmitted stamped with no exceptions by John Buchanan on 5/8/19  


5/8/2019 jbranton

2.)  Since there has been major changes in plans dealing with fire pump, hydrant and FDC removal, and this does not reflect the original approved DRC plans,  A DRC resubmittal is required.

 

Contact Stephanie Murray @ 904-209-1742 for questions concerning DRC

A modcp was submitted and approved on 4/15/19 which removed the fire pump but the hydrant and on building FDC remains. 4/16/19 JSB

4/16/2019 jbranton