Plan reviewed for 10340sf construction type IIB fire sprinklered (and alarmed) building to be used as a motor vehicle repair garage. It appears that it was submitted as a storage occupancy only. Reviewed as mixed storage (unsure of classification) and special purpose industrial using FFPC 6th edition effective Dec. 31, 2017. Reviewer: Sandra Boike 904 209 1741 Victoria Vitori 904 209 1748 To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
|
| |
|
|
RESUBMITTING: Please make necessary changes and resubmit the complete permit application package.
To help speed the review process you should include a written comment response summary to clarify or illustrate corrections on plans (bubbling, highlighting or notations are best). Please use the Florida Fire Prevention Code 6th Ed for all code reference in a response to comments. The fire plans examiner does not use the Florida Building Code. You are required to remove old pages and reinsert the new pages.
The numbered items require a response or plans to be updated to complete the review. Items labled "informational only" are for the contractor.
|
| |
|
|
1) Code summary appears to address the 5th edition of the Florida Fire Prevention Code. As of Jan. 1, 2018 the state adopted FFPC 6th edition. Please update. FAC 69a-60.005
|
| |
|
|
2) The illustrated occupancy classification for the building is "S-1". Please update Code Summary to include:
- Storage classification (low, ordinary or high). 101:42.1.5
NTOE: Unable to check compliance with 101:42.2.4., 101:42.2.5, 101:42.2.6 since no classification indicated. This will be checked once classification indicated on plan.
- All occupancy classifications along with subclassification (special purpose industrial 1:30.2.2) and commodity classification (class and group 1:34.2) according to fire code. 1:30.2.2
|
| |
|
|
3) The listed mezzanine square footage is 820sf. The listed "parts" room square footage is 1520sf. The mezzanine appears to exceed the "one-third the open area of the room in which the mezzanine" is located allowance. 101:8.6.10.2 Please address.
|
| |
|
|
4) How is there only 1 means of egress for the "mezzanine"? 101:40.2.4.1.1
NOTE: Common path of travel is not met for the mezzanine either at this time. 101:40.2.5.1
|
| |
|
|
5) Will storage be considered high piled storage? If so please illustrate compliance with 1:20.15.8.
|
| |
|
|
6) Page DE1 shows a tire dumpster. Will tires be stored inside? If so be prepared to point out compliance with 1:34.8.
|
| |
|
|
INFORMATIONAL ONLY NO RESPONSE NECESSARY: The system(s) outlined in this set of plans is conceptual.
A HOLD has been placed at framing (105) until a permit application has been submitted. - fire alarm system (page A.0 and E3) - fire sprinkler system (FP pages) - fire underground (including hydrant) - tank permit for 1000 gal AST tank shown on page DE1 near dumpster - tank permit for propane tank shown on page C3.0 NE of building in parking lot - fire pump
|
4/25/2018
| VVitori |
|
|
A fire department access box is required due to fire protection in the building. The brand approved by our department is fail safe. It will need to be mounted at building entrance. Use the link below to order the box off of their website. It is imperative to fill in all the sections with the correct information to ensure your access box is keyed properly. The required box for this jurisdiction is the "LBI FAIL- SAFE- LOCK BOX WITH TAMPER SWITCH". This is usually the first box listed and is approx. $225.OO. Remember when the form references the fire “department/ issuing agency” and “authorized signature” you must indicate " St. Johns County Fire Rescue". https://www.nutechlink.com/failsafeordering/index.html
|
4/25/2018
| VVitori |
|
|
7) Will the repair garage service vehicles that use non-odorized gases (e.g. hydrogen, LNG, CNG)? If so please point out compliance with 1:30.2.8.
|
| |
|
|
8) Page PP2 shows a 1000g tank. What is this for? Is this going near tire dumpster?
NOTE: Page PP7 shows oil water separator as 600g.
|
| |
|
|
9) Multiple fire alarm devices shown on page E3.An ENGINEERED signed and sealed Design Criteria for the fire alarm system over $5000.00 is required to be submitted with the general construction documents. FAC 61G15-32.002(5) We are unable to approve the plan until this information is provided. (The Design Criteria is not a full set of shop drawings.) THIS IS WHAT IS REQUIRED BY FLORIDA ADMINISTRATIVE CODE 61G15-32.008,(A-O) Design of Fire Alarms and Detection Systems.
|
| |
|
|
10) FP pages show sprinkler system information but does not outline all design criteria. An ENGINEERED sealed Design Criteria for a fire sprinkler system exceeding 49 heads is required to be submitted with the general construction documents. We are unable to approve the plan until this information is provided. (FAC 61G15-32.002(5)) (The signed and sealed design criteria is the general guidelines with design and scope of the sprinkler system. It is not a full set of shop drawing.) THIS IS WHAT IS REQUIRED BY FLORIDA ADMINISTRATIVE CODE 61G15-32.004, (A-M) as of June 19th, 2015, Design of Water Based Fire Protection Systems.
|
| |
|
|
11) Page A8 appears to show stair and mezzanine guards that do not meet 101:7.2.2.4.6.3. Please address.
|
| |