SJC Home
Clearance Sheet C2018-000050*003

 Department IssuesSigned OffIntl

Plans for a 1080 square foot interior remodel in a building that has a sprinkler and a fire alarm.  Plan reviewed as business.  The plans is rejected for the following reason. 


                                                        
Reviewed using FFPC 6th edition effective Dec. 31, 2017.
Reviewer: PJ Webb 904 209 1744
 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

 

Emergency lights

Provide specifications for proposed emergency lights.  Based on what I have found for the Cooper Apel light (proposed), the lights are listed at 17 foot spacing which is exceeded in the plans.  In addition most devices are listed for 7.5 feet mounting height.   If this is the case will the 8' partition walls obstruct the light.  It appears additional lights will be needed. 

Also ensure that the light reach is sufficient to reach the designated egress path. 

 

INFORMATIONAL ONLY NO RESPONSE NECESSARY:
The system(s) outlined in this set of plans is conceptual.

A HOLD has been placed at framing (105) until either: a) a permit has been pulled or b) a letter submitted from respective system contractor indicating no work to be done to the existing system:
- fire alarm system
- fire sprinkler system